2 2
I-T-E Pressure Wire Connectors
General
NOTE: This instruction outlines the recommended installation
procedure for all MD and ND Frame pressure wire
connectors.
A.
Move breaker handle to OFF position, or depress PUSH
TO TRIP button. Breaker must be in OFF or TRIPPED
position before continuing.
B.
Remove terminal shield (1) (Figure 2) (two #6-32 screws.)
C.
Mount breaker securely. See circuit breaker instructions
for proper installation procedures.
D.
Mount pressure wire connectors (2) to terminal pads (3)
with mounting screws (4) (Figure 1). Recommended
torque is 228 in. Ib.
NOTE: Steps C and D may be completed in any convenient
order.
E.
Attach power cables to connectors and tighten set
screws (5) (Figure 1) to specifications per Table 1.
NOTE: Cables must extend straight for at least 4 inches from
face of connector to clear shield.
F
Mount removable terminal shield (6) (Figure 2) to end of
circuit breaker. Shield should be flush with end of circuit
breaker.
G.
Re-assemble terminal shield.
NOTE: When terminal cover is properly installed, wire con-
nector shield should be held securely.
NOTE: End barrier NDTS is supplied with kits 2 TA4P8500,
3TA4P8500, 2TA3P8750, 3TA3P8750, 2TA2K8750,
3TA2K8750. Barrier can be purchased as a separate
item for use with other terminal connectors.
Figure 1
Figure 2
Содержание I-T-E Sensitrip MD Series
Страница 2: ......
Страница 6: ...4 I T E Sensitrip Digital Circuit Breaker MD and ND Frame Outline Drawings 1 3 Pole ...
Страница 8: ...6 MD and ND Frame Trip Adjustments ...
Страница 12: ...10 MD and ND Frame Time Current Curve 600 1000A With Short Time Delay Set on Fixed Time ...
Страница 13: ...MD and ND Frame Time Current Curve 11 1200A With Short Time Delay Set on Fixed Time ...
Страница 14: ...12 MD and ND Frame Time Current Curve 600 100A With Short Time Delay Set on I2 t ...
Страница 15: ...MD and ND Frame Time Current Curve 13 1200A With Short Time Delay Set on I2 t ...
Страница 16: ...14 MD and ND Frame Time Current Curve 600 100A Without Short Time Settings ...
Страница 17: ...MD and ND Frame Time Current Curve 15 1200A Without Short Time Settings ...
Страница 18: ...16 MD and ND Frame Time Current Curve Ground Fault Trip Data ...
Страница 19: ...MD and ND Frame Time Current Curve 17 Example ...
Страница 20: ...18 MD and ND Frame Let Thru Curves ...
Страница 31: ...Installation Diagrams 29 ...
Страница 35: ...I T E Mechanical Interlock M15404 33 Figure 7 ...
Страница 41: ...Installation Diagrams 39 ...
Страница 49: ...Installation Diagrams 47 ...
Страница 50: ...48 I T E Panelboard Connecting Straps 1 ...
Страница 53: ...Installation Diagrams 51 ...