20
Removing BQD circuit breakers
from panel
1. Disconnect and lock off all power
sources supplying this panel.
2. Remove P1 Panel trim and deadfront.
3. If the SIPOD is connected to the BQD
breaker, unplug the SIPOD connector
from the data rail connection, remove
the load wire attached to the SIPOD load
terminal and loosen the BQD load lug to
remove the SIPOD.
4. Remove the screw connecting the BQD
line bar connection to the panel bus bar.
5. Grip the BQD breaker and pull it in the
direction towards the center of the panel
or away from the top barrier to remove it.
SIPOD description
SIPOD is a remotely operated electro-
mechanical contactor device that is
attached to Siemens BQD molded case
circuit breaker. The purpose of a SIPOD is
to allow switching of a load, ON and OFF,
from a remote location or according
to a pre-arranged time schedule.
The SIPOD will connect to the load side of
the breaker using a conductor tab inserted
into the breaker load lug. The wiring to the
loads will be connected to the load lug of
the SIPOD, which is the same size as the
circuit breaker load lug.
The SIPOD communicates with the
controller in the P1 Lighting Panel via
a 4-wire connection to the data rail.
The 4 wire connections to the data
rail are:
•
A common line
•
A 24 volt power for the electronics and
operation of the solenoid
•
A selector line used by the I/O Controller
Board to select a SIPOD
•
A communication line
Chapter 6
System components
DANGER
Hazardous voltage.
Will cause death or
serious injury.
Keep out.
Qualifi ed personnel only.
Disconnect and lock off all
power before working on
this equipment.