8 Specifications
8.1 Technical data
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
●
Document 007001
●
Document 008345
Detector line
Operating voltage
DC 12…33 V
Operating current (quiescent)
200 μA
Maximum current connection factor
1
Quiescent current connection factor
1
Address connection factor
1
Separator connector factor
1
Protocol
FDnet/C-NET
System compatibility
See 'List of compatibility'
Line separator
Line voltage:
●
Nominal
●
Minimum
●
Maximum
DC 32 V (= V
nom
)
DC 12 V (= V
min
)
DC 33 V (= V
max
)
Voltage at which the line separator
opens:
●
Minimum
●
Maximum
DC 7,5 V (= V
SO min
)
DC 10.5 V (= V
SO max
)
Permanent current when switches are
closed
Max. 1.5 A (= I
C max
)
Switching current (e.g., in the event of
a short-circuit)
Max. 2 A (= I
S max
)
Leakage current when switches are
open
Max. 1 mA (= I
L max
)
Serial impedance when switches are
closed
Max. 0.4 Ω (= Z
C max
)
The line separator is closed via an actuation signal from the control panel. Required line voltage: DC 12…33 V
(normal range)
External alarm indicators Number of external alarm indicators
that can be connected
2
Voltage
DC 10…17 V
Current
9…15 mA
Length of line
●
Max. 30 m with unshielded cables, or
when the shielding is connected to the
positive pole of the detector base
●
Max. 5 m, if the shielding is connected
to earth
Specifications
Technical data
8