Manual call point FDM224H
w
The manual call point is installed and electrically connected. See the chapter
'Installation [➙ 31]'.
1. Set the detector line to 'Test' on the control panel.
2. Open the door of the manual call point with the Allen key.
a
The alarm signal is transmitted.
3. Check whether an alarm is displayed on the fire control panel.
4. Close the door of the manual call point.
a
The manual call point is ready for operation again.
5. Set the detector line to 'Normal operation' on the control panel.
a
The detector line is ready for operation again.
Commissioning
Checking function