3.3.5 Interface to service devices
A proximity interface (MC link) is available for commissioning and maintenance in
order to communicate with the detector exchanger and tester FDUD292 and the
intelligent detector tester FDUD293.
You will find additional information in documents 007227 and 009718.
See also
2
3.3.6 Diagnosis levels
The manual call point monitors its operation largely autonomously.
The following diagnosis levels are derived from the different control measurements:
●
Normal
●
Replacement necessary
●
Fault
For details, see table below.
When an error occurs which impairs the correct functionality of the device, a fault
message is reported to the control panel.
To remedy the cause, additional information is available in the manual call point.
This can be displayed by the detector exchanger and tester FDUD292 or the
intelligent detector tester FDUD293, for example.
You will find additional information in documents 007227 and 009718.
Information displayed on
the detector exchanger
and tester
Meaning
Measures
'No deviation'
Normal, no fault is present
The manual call point is fully functional
None
'needed excha.'
1
Replacement necessary
Key monitoring outside the tolerance
range
Replace manual call point
Other fault message
2
Fault present
●
Alarming no longer guaranteed
●
Key monitoring outside the
tolerance range or malfunctioning
due to external influences
Replace manual call point
Supply error
●
Check detector line voltage
●
Replace manual call point
Software error (Watchdog error)
Replace manual call point
Memory error
Replace manual call point
Communication error between the
manual call point and the control panel
Remedy cause
1
The information displayed on the detector exchanger and tester is always in
English; no translation into the corresponding language.
2
This status can be displayed together with other statuses, e.g. 'needed
excha.' (replacement necessary).
See also
2
Structure and function
Function
3
20 | 54
007002_k_en_--