5.2 Installation
Observe the country-specific regulations for the exact installation height!
Manual call points FDM223 and FDM224 (housing FDMH293-x or
FDMH297-R)
w
The manual call point FDM223/FDM224 is prepared for installation. See the
chapter 'Preparing the housing'.
1. Secure the housing at a height of 0.9…1.6 m on an even surface.
–
If you are using housing FDMH293-x: In wet areas, only use the screw
holes marked by arrows (see diagram below).
–
Housing FDMH297-R may not be used in wet areas.
2. Pull the cables through the entry opening(s) into the housing.
–
Cable entry from the rear of the housing is only permitted for housing
FDMH297-R.
–
In wet areas, use metal cable glands M20 x 1.5 (accessories).
a
The manual call point FDM223/FDM224 is now prepared for electrical
connection.
Figure 9: Screw holes in housing FDMH293-x
Figure 10: Housing FDMH297-R with breakout points for cable entries and screws (cable entries and
screw holes are compatible with old housings)
Mounting / Installation
Installation
5
007002_k_en_--
29 | 54