Manual call point FDM224
w
The manual call point is installed and electrically connected. See the chapter
'Installation [➙ 31]'.
1. Set the detector line to 'Test' on the control panel.
2. Push the keyhole cover to the right.
3. Open the door of the manual call point with the key.
a
The alarm signal is transmitted.
4. Check whether an alarm is displayed on the fire control panel.
5. Pull out the key.
6. Push the keyhole cover back into place.
7. Close the door of the manual call point.
a
The manual call point is ready for operation again.
8. Set the detector line to 'Normal operation' on the control panel.
a
The detector line is ready for operation again.
Commissioning
Checking function
6
40 | 54
007002_k_en_--