![Siemens FDCIO223 Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/siemens/fdcio223/fdcio223_technical-manual_377133050.webp)
Planning
Compatibility
4
50 | 72
Building Technologies
009122_h_en_--
Fire Safety
2016-05-04
4 Planning
When planning a project, proceed as follows:
1. Define the mounting site and configuration of the lines
2. Plan the various line types:
– Collective detector line
– Collective detector line for areas at risk of explosion (zone 1 and zone 2)
– Conventional detector line
– Control lines
– Contact inputs
4.1 Compatibility
The input/output module FDCIO223 is compatible with the following fire detection
systems:
Sinteso FS20
Cerberus PRO FS720
SIGMASYS
AlgoRex
Detector line
Control panel
FC20xx
FC72x
SIGMASYS
AlgoRex
FDnet
X
-
X
X
C-NET
–
X
–
–
X = compatible
– = not compatible
You will find detailed information in the 'List of compatibility'.
Limitations
Maximum of 32 devices per collective detector line if each device has a KMK =
1
If devices have a KMK >1, the maximum number of devices per collective
detector line decreases accordingly.
See also