Structure and function
Input/output configuration options (secondary side)
3
34 | 72
Building Technologies
009122_h_en_--
Fire Safety
2016-05-04
3.4.2.2 Conventional detectors which can be connected
Conventional detector line configured as SynoLINE300:
– Synova 300 series fire detector
Third-party products in accordance with 'Industrial conventional', e.g.:
– Apollo Series 65
– Apollo Orbis
You will find an overview of the detectors that can be connected in the 'List of
compatibility':
For fire detection systems FS20: Document 008331
For fire detection systems
FS720:
Document A6V10229261
Using manual call points
Some manual call points, such as the MT320C and FDM1101A-Rx, are supplied
without an alarm resistor. These manual call points only contain a switching
contact.
In order to ensure that these manual call points function correctly, you must
connect an alarm resistor R
A
with the following values to the manual call point:
R
A
= 620 ±5 %, P = 1 W
The following table shows how to connect alarm resistor R
A
correctly:
FDM1101A-Rx
MT320C
EOL and R
L
are end-of-lines for a specific control panel.
You will find more specific information on using manual call points FDM1101A-Rx
and MT320 in documents A6V10201154 and 007904.
LINE
LINE
+
+
FDM1101A-Rx
EOL
R
A
R
L
R
A