DEVICE PROGRAMMING UNIT USER’S MANUAL
|
CHAPTER 2
20
PROGRAMMING
Press EXIT to return to the Main Menu. Press RE-
DO to reprogram the device.
•
If the TRI was programmed correctly and the device
is removed, the ”searching” screen will display.
Changing a Device ID
The ID of certain MXL detectors may be changed for
backward compatibility. The DPU Programming mode
provides the capability to accomplish this.
With the DPU displaying the Main Menu, press the
PROGRAM button. The DPU will prompt the user to
insert or connect a device or detector. When the DPU
finds the detector, it will display the detector type.
Following is an example screen:
FP-11
LOOP=012 ADDRESS=41
<ID
SETTINGS>
<EXIT PROGRAM>
Press the ID button. The display will be similar to the
following:
FP-11, 012-41
SELECT THE NEW ID
ID-60P/PT>
<EXIT OK?>
Press the ID-60P/PT button to cycle through the possible
IDs that may be set. The DPU will only present IDs that
the device will accept. When the ID is set correctly,
press OK to return to the programming mode to finish
programming the device or press EXIT to return to the
programming mode without changing the ID.
Table 1 lists all backward compatible devices and the
devices the DPU will allow them to emulate.