DEVICE PROGRAMMING UNIT USER’S MANUAL
|
CHAPTER 2
14
PROGRAMMING
•
To adjust the LOOP and ADDRESS settings, press
SETTINGS. The DPU will display a screen similar to
the following:
FP-11
LOOP=012 ADDRESS=41
<LOOP ADDRESS>
<EXIT PROGRAM>
Press the LOOP or ADDRESS button to move the
cursor over the loop or address number, and then
use the keypad to set the appropriate number.
The loop number is limited to 246 and will only appear if the
DPU has been configured for label printing.
•
If the loop and address information is correct, press
PROGRAM. The DPU will indicate that it is program-
ming the unit and when programming is complete,
will display a screen similar to the following:
FP-11
LOOP=012 ADDRESS=41
PROGRAMMED OK
<EXIT CHANGE>
Press EXIT to return to the Main Menu. Press
CHANGE to return to the beginning and change the
settings.
The MXL device address range is 01 to 60. If the
data entered is out of range, the following screen
will flash for 3 seconds:
INCORRECT ENTRY!!!
If the smoke detector was not programmed
correctly, the display will show a screen similar to
the following:
FP-11
LOOP=012 ADDRESS=41
PROGRAMMING FAILED
<EXIT RE-DO>