background image

 

Building Technologies 

Fire Safety & Security Products 

 

 

 

 

 

DMS8000 MP4.10 

Application & 
Planning 

For: 
 - MM8000 Management Station 
 - MK8000 OPC Server 
 - MT8001  Management Terminal 
 - NK8000  Networks 

With WW8000 Composer

 

Содержание DMS8000

Страница 1: ...Building Technologies Fire Safety Security Products DMS8000 MP4 10 Application Planning For MM8000 Management Station MK8000 OPC Server MT8001 Management Terminal NK8000 Networks With WW8000 Composer ...

Страница 2: ...ument and in the subject thereof By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him ...

Страница 3: ...3 3 3 1 ISO1745 direct configuration 23 3 3 2 Cerloop configuration 25 3 3 3 CS1115 FC330A direct configuration 27 3 3 4 SI410 420 Sintony direct configuration 28 3 3 5 Video LAN configuration 30 3 3 6 Access control LAN configuration 32 3 3 7 BACnet IP LAN configuration 34 3 3 8 Remote notification configuration 35 3 3 9 OPC integration configuration 36 3 3 10 NK822x serial configuration 37 3 3 1...

Страница 4: ...t components 62 5 2 2 Application example with Industrial Ethernet components 63 5 2 3 Application example with OTN Open Transport Network 65 5 3 Shared network 66 5 3 1 Information you need to give to your customer 67 5 3 2 Security and Application Port numbers 67 5 4 Datalink characteristics 68 5 4 1 LON 68 5 4 2 Serial interface RSxxx 68 5 4 3 Modems 68 5 4 4 Ethernet 69 5 4 5 FDDI CDDI 70 5 4 ...

Страница 5: ...ne the appropriate products and configurations in order to produce a quotation They provide customers and consultants with the basic information necessary to begin installation configura tion and commissioning activities Liability disclaimer We have taken every possible care in preparing this manual The contents of this manual are revised regularly and brought up to latest standards Nevertheless w...

Страница 6: ...r in the Brochure No field e g A6V10062415 or 007121 and press Enter Hint For a specific version specify the Market Package as MPn nn in the Classi fication No field e g MP4 10 Note STEP provides no results when the number of found objects is equal to or greater than 200 Product and Document Name Document no Date Last up date Sales documents MM8000 023 Product Datasheet A6V10062415_a 06 2007 MP4 1...

Страница 7: ...Notes MP2 20 007145_b 7 2003 MP2 20 073 Release Notes MP2 10 007090_a 04 2003 MP2 10 048 Autronica BSxx ICC ad on 008750_a 06 2006 MP3 20 048 LIST SCU 2000 ICC add on 009248_a 06 2006 MP3 20 048 MAXSYS PC601 ICC add on 008751_a 06 2006 MP3 20 048 CP100 ICC add on 009848_a 06 2006 MP3 20 048 R Card M5 ICC add on A6V10064742_a 06 2007 MP4 10 048 MODBUS ICC add on A6V10067800_a 06 2006 MP3 20 048 CDD...

Страница 8: ...0 2003 MP1 30 019 NK8223 CDI Net 007154_b 10 2003 MP1 30 019 CS6 Guarto 007545_b 02 2004 MP1 31 019 SI410 Sintony 008597_a 12 2004 MP3 10 019 CC60 007547_b 10 2003 MP1 30 019 NK822x 007879_b 02 2004 MP1 31 019 CF9000 007880_a 10 2003 MP1 30 019 SIMATRIX 007881_a 02 2004 MP1 31 019 Philips Burle CCTV 008085_a 02 2004 MP1 31 019 SiPass 008607_a 03 2006 MP3 20 019 TELSCAN 009426_a 03 2006 MP3 20 019 ...

Страница 9: ...V10065253_a 06 2007 MP4 10 048 Graphical Map Configuration A6V10062441_a 06 2007 MP4 10 022 Graphical Map Config Quick Ref A6V10069550_a 06 2007 MP4 10 016 Migration from DMS7000 A6V10062443_a 06 2007 MP4 10 MK8000 OPC Server In addition to the documents available through the STEP documentation system the OPC Foundation publishes a number of other documents that are necessary and or useful for und...

Страница 10: ...d elements as Automatic detectors Manual call points Signalling devices contacts Control elements The individual elements are usually combined in alarm zones and are connected to the control unit Automation level configu ration The Automation level configuration relates to the variety of possible connections of subsystems control panels such as AlgoRex via possible network structures to the DMS co...

Страница 11: ...ions MM8000 Management Station The MM8000 provides integrated management and handling decentralised system operation and centralised maintenance The MM8000 is designed to replace older management stations such as LMSmodular LMS6 and DMS7000 MM8000 also offers the following advantages Flexibility The system can be built and configured to fit different situations Scalability MM8000 will easily grow ...

Страница 12: ... DMS8000 systems NK8225 Ethernet Port with BACnet Gateway for DMS8000 systems 1 2 1 NK8222 NK8223 or NK8225 The NK822x Ethernet Ports are used to connect local and distributed safety and secu rity devices to the NK8000 network The NK822x port provides a first level of centrali sation and acts as a secure communication partner for DMS8000 All ports come with optional housing solutions with autonomo...

Страница 13: ...ort of switched lines Simultaneous multiple host connectivity up to four using CMSDL IP protocol with out encryption Upstream serial connectivity to a local management station MM8000 MK8000 MT8001 using an RS232 line via CMSDL serial protocol The upstream devices MM8000 or MK8000 must be equipped with the NS8210 Network Driver for TCP IP on Ethernet connectivity or with the NS8012 CDI Net Driver f...

Страница 14: ...y connected subsystems CS11 AlgoRex SIGMASYS D100 SI410 420 Sintony CS6 Guarto CF9000 Philips Burle Optional dial up connectivity via modem for wide area extension systems 1 3 Configuration WW8000 Composer MM8000 MK8000 MT8001 and NK8000 can be configured in a fast safe and easy way with Composer using the subsystem tool concept Composer is the common configuration tool for all DMS8000 products Fo...

Страница 15: ...y options refer to Appendix A 2 1 MM8000 Management Station MK8000 OPC Server configura tions The following management configuration types are supported in MM8000 MK8000 Stand alone station Client server configuration Distributed configuration which may include SiPass access control and or CCTV Redundant solution configuration 2 1 1 Stand alone configurations Characteristics Stand alone station th...

Страница 16: ...tion is specialised for a single function Optional redundancy solution with dual servers to prevent service interruption MM8000 The client provides the user interface The server handles all the func tionality provided by MM8000 and holds the configuration database The FEP Front end processor provides the drivers for the different network connections such as Cerloop NK8000 etc New MM8000 now provid...

Страница 17: ...oducts 06 2007 The following are examples of distributed configurations Fig 3 MM8000 MK8000 redundant configuration with dual servers Note For technical details regarding a redundancy configuration solution please con tact customer support Fig 4 MM8000 MK8000 SiPass distributed configuration Note MM8000 MK8000 and SiPass servers may reside separately ...

Страница 18: ...ours hosts for MM8000 MK8000 2 2 1 DMS8000 Multiple host configuration CMSDL IP Characteristics Communication layer equipped with NS8210 Network driver Up to four hosts Fig 5 NK8225 DMS8000 CMSDL multiple host configuration 2 2 2 DMS8000 multiple host configuration BACnet IP Characteristics Communication layer equipped with NS8011 BACnet Network Driver for DMS8000 Conversion of native protocols to...

Страница 19: ...710_a_en Fire Security Products 06 2007 2 2 3 DMS8000 single host configuration support of dial up connections Characteristics Communication layer equipped with NS8210 Network driver and modem s NK822x dial ups as primary no Ethernet connection or secondary in case net work is down via PSTN Fig 7 NK8000 dial up configuration ...

Страница 20: ...k components NK822x MK7022 GW 21 GW 20 Control units Note For control unit versions see MM8000 MP4 10 Release Notes STEP A6V10062455 Fire detection systems CS11 AlgoRex FC700A CS1115 FC330A CZ10 STT11 Système de Télécommande et Télésignalisation STT20 STT2410 SIGMASYS D100 Intrusion detection systems CS4 SI410 420 Sintony CS440 CZ12 CS6 Guarto Gas detection systems CC60 Video systems SIMATRIX SIMA...

Страница 21: ...n DESIGO PX General automation and I O systems SIMATIC S7 MF7033 MM7033 digital PLC unit CF9000 I O systems Remote notification ESPA Paging System 3 rd party systems A number of 3 rd party systems are supported via NK822x or MM8000 drivers For details see section 3 5 Section 3 3 details the configuration types supported by MM8000 and MK8000 Note Combinations of automation level configurations are ...

Страница 22: ...232 Cerloop NK8000 local host requires NK8000 MP3 15 Network components MK7022 NK822x requires NK822x MP3 15 Control units Fire detection systems CS11 AlgoRex FC700A CZ10 STT11 Système de Télécommande et Télésignalisation Intrusion detection systems SI410 420 Sintony CS440 CS6 Guarto Gas detection systems CC60 General I O systems MF7033 MM7033 digital PLC unit CF9000 I O systems Section 3 3 detail...

Страница 23: ...SO1745 direct configuration System architecture This configuration allows for integration of CS11 AlgoRex or FC700A fire panels The CK1142 or FG700A provides the liaison to MM8000 MK8000 MT8001 Communication connection The upstream side of the gateway CK1142 or FG700A is connected to the DMS via serial line The downstream side of the gateway is connected to one or more CS11 AlgoRex or FC700A fire ...

Страница 24: ...teway for CS11 CK1142 Gateway for FC700A FG700A Additional components required for the various management station types Type Additional components Name Version Foreign station OPC client head end Any OPC DA2 0x compliant client OPC DA2 0x OPC Server MK8000 MP4 10 ISO1745 Driver NS8010 MM8000 ISO1745 Driver NS8010 MP4 10 MT8001 None MP3 15 Limits and restrictions Type Version Restrictions MM8000 MK...

Страница 25: ... allows for integration of a number of Cerloop proprietary Class A loop connectable control panels The MK7022 provides the liaison to MM8000 MK8000 MT8001 Communication connection The upstream side of the MK7022 gateway is connected to the DMS via serial line The downstream side of the MK7022 is connected via Cerloop to different fire secu rity control units A CS11 AlgoRex cluster can be connected...

Страница 26: ...rloop MK7022 Gateway for CS11 CK1142 Gateway for STT11 SK11 Additional components required for the various management station types Type Additional components Name Version Foreign station OPC client head end Any OPC DA2 0x compliant client OPC DA2 0x OPC Server MK8000 MP4 10 ISO1745 Driver NS8010 MM8000 ISO1745 Driver NS8010 MP4 10 MT8001 None MP3 15 Limits and restrictions Type Version Restrictio...

Страница 27: ...32 Subsystems that can be connected in this way Supported by Type Name MM8000 MP4 10 MK8000 MP4 10 MT8001 MP3 15 Fire panel CS1115 FC330A X X X X Additional components required for the various management station types Type Additional components Name Version Foreign station OPC client head end Any OPC DA2 0x compliant client OPC DA2 0x OPC Server MK8000 MP4 10 Fire CNDL Driver NS8015 MM8000 Fire CN...

Страница 28: ...ion via RS 232 Fig 12 Serial configuration via LAN tunnelling System architecture This configuration allows for integration of SI410 420 Sintony intrusion panels Communication connection The connection can be via Serial line RS 232 LAN where the SI410 420 is equipped with a SMN36 serial LAN adapter On the management station a software module provides a virtual COM port External adapter e g LANTRON...

Страница 29: ...tional components required for the various management station types Type Additional components Name Version Foreign station OPC client head end Any OPC DA2 0x compliant client OPC DA2 0x OPC Server MK8000 MP4 10 SI410 420 Sintony driver NS8014 LAN RS 232 software for LAN tunnelling LANTRONIX redirector or equivalent See LANTRONIX documentation MM8000 SI410 420 Sintony driver NS8014 MP4 10 LAN RS 2...

Страница 30: ...000 Communication connection The CCTV devices are connected to the DMS via LAN Subsystems that can be connected in this way Supported by Type Name MM8000 MP4 10 MK8000 MP4 10 MT8001 MP3 15 CCTV SISTORE AX X X SISTORE CX X X SISTORE MX X X SISTORE MXpro X X SISTORE SX X X TELSCAN video web server X X IP cameras fixed 3 rd party systems See DMS8000 Video Connectivity Configu ration guide STEP A6V100...

Страница 31: ...A2 0x OPC Server MK8000 MP4 10 Appropriate software according to specific device SISTORE TELSCAN MM8000 Appropriate software according to specific device SISTORE TELSCAN 3 rd party systems MP4 10 IP camera devices CCIS1337 LP CFVA IP CVVA IP See section 3 5 on page 54 and DMS8000 Video Connectivity Configuration guide STEP A6V10062457 for supported 3 rd party subsystems Limits and restrictions Typ...

Страница 32: ... The Advanced Central Controller s either SiPass ACC or Cerpass CC30 via SiPass manages communication between devices and the DMS SiPass server via LAN Note The SiPass server can be separate from the MM8000 MK8000 server Subsystems that can be connected in this way Supported by Type Name Version MM8000 MP4 10 MK8000 MP4 10 MT8001 MP3 15 Access control SiPass Integrated X X 3 rd party systems See D...

Страница 33: ...onents required for the various management station types Type Additional components Name Version Foreign station OPC client head end Any OPC DA2 0x compliant client OPC DA2 0x OPC Server MK8000 MP4 10 MM8000 MK8000 Access Control software SiPass Integrated SiPass Driver NS8018 Limits and restrictions Type Version Restrictions MM8000 MK8000 MP4 10 None MT8001 MP3 15 Not supported ...

Страница 34: ...0 MP4 10 MK8000 MP4 10 MT8001 MP3 15 Building automation DESIGO PX X Additional components required for the various management station types Type Additional components Name Version Foreign station OPC client head end Any OPC DA2 0x compliant client OPC DA2 0x OPC Server MK8000 MP4 10 BACnet Driver NS8011 MM8000 BACnet Driver NS8011 MP4 10 Limits and restrictions Type Version Restrictions MM8000 MP...

Страница 35: ...onnection The paging system is connected to the DMS via RS 232 Subsystems that can be connected in this way Supported by Type Name Version MM8000 MP4 10 MK8000 MP4 10 MT8001 MP3 15 Paging System ESPA compliant paging devices X Additional components required for the various management station types Type Additional components Name Version MM8000 Paging dispatching services Limits and restrictions Ty...

Страница 36: ... RCO R Card M5 Communication connection 3 rd party subsystems are connected via Ethernet to the OPC server which may run on the MM8000 Management Station or on a networked PC MM8000 connects to the OPC server for all of the communication to from the subsystems Subsystems that can be connected in this way Supported by Type Name Version MM8000 MP4 10 MK8000 MP4 10 MT8001 MP3 15 I O System SIMATIC S7...

Страница 37: ...nectable control panels In addition it allows for Guarto CS6 integration via LON bus One of the NK822x Serial Ports provides the li aison for a local management station MM8000 MK8000 Communication connection The NK822x is connected on upstream side via RS 232 proprietary CMSDL protocol to the management system Note A temporary Ethernet network link is required for configuration download On the dow...

Страница 38: ...X Intrusion panel CZ12 X X Intrusion panel SI410 420 Sintony X X Intrusion panel CS6 Guarto X X Gas panel CC60 X X Digital PLC unit MF MM7033 X X Système de Té lécommande et Télésignalisation STT11 STT20 STT2410 X X X X Video Crossbar SIMATRIX X X Video Crossbar SIMATRIX NEO X X Input Output CF9000 and DF8020 40 excluding DF8045 46 X X 3 rd party systems See section 3 5 on page 54 for supported 3 ...

Страница 39: ...ents Name Version Foreign station OPC client head end Any OPC DA2 0x compliant client OPC DA2 0x OPC Server MK8000 MP4 10 CDI Net Driver NS8012 MM8000 CDI Net Driver NS8012 MP4 10 Limits and restrictions Type Version Restrictions MM8000 MK8000 MP4 10 Upstream serial connectivity is limited to one host Host must be equipped with NS8012 CDI Net Driver NS8012 CDI Net Driver supports max 3 NK822x s MT...

Страница 40: ...vide the liaison to MM8000 MK8000 Additionally the NK822x provides serial connectivity to a local host MM8000 MK8000 MT8001 using an RS 232 line via CMSDL protocol Communication connection The NK822x is connected on the upstream side via Ethernet to the MM8000 and or the MK8000 and on the downstream side via serial lines and or via LON bus to a number of different fire security control units Dial ...

Страница 41: ...X Intrusion panel CZ12 X X Intrusion panel SI410 420 Sintony X X Intrusion panel CS6 Guarto X X Gas panel CC60 X X Digital PLC unit MF MM7033 X X Système de Té lécommande et Télésignalisation STT11 STT20 STT2410 X X X X Video Crossbar SIMATRIX X X Video Crossbar SIMATRIX NEO X X Input Output CF9000 and DF8020 40 excluding DF8045 46 X X 3 rd party systems See section 3 5 on page 54 for supported 3 ...

Страница 42: ...rsion Restrictions MM8000 MK8000 MP4 10 NK822x supports logical connections to a max of 4 hosts MM8000 and or MK8000 via CMSDL IP protocol Only one host can be supported using the CEI 79 5 en crypted protocol Up to 500 NK822x can be connected to an MM8000 MK8000 however please contact customer support for configurations of over 100 Upstream serial connectivity is limited to one host Up to four CS6...

Страница 43: ...ure This configuration allows for integration of fire and intrusion detection systems Communication connection The NK8225 is connected on upstream side via Ethernet to MM8000 and or MK8000 BACnet On the downstream side it is connected via serial lines and or via LON bus to a number of different fire security control units For supported downstream configurations protocols of NK8225 please refer to ...

Страница 44: ...trusion panel SI410 420 Sintony X X Intrusion panel CS6 Guarto X X Network devices required Type Name Version Ethernet Port with BACnet Gateway NK8225 MP4 10 Gateway for CS11 CK1142 Gateway for FC700A FG700A Additional components required for the various management station types Type Additional components Name Version Foreign station OPC client head end Any OPC DA2 0x compliant client OPC DA2 0x O...

Страница 45: ... and network wide interactions via BACnet are currently not compatible Up to four CS6 Guarto intrusion panels per NK8225 are supported NK8000 requires static IP addresses i e DHCP is not supported Default UDP Port 47808 hex BAC0 for BACnet con nectivity configurable BACnet Broadcast Management Device BBMD is sup ported in NK8225 NK8225 can be installed on different TCP IP subnets Max 150 COV subsc...

Страница 46: ...tension 1 Ethernet line for remote station 4 serial lines for subsystems local station modem NK8223 CL2 NK8225 CL2 Base module LON extension 1 Ethernet line for remote station 1 LON line for subsystems 2 serial lines for subsystems local station modem NK8223 CL4 NK8225 CL4 Base module LON and 2 port extensions 1 Ethernet line for remote station 1 LON line for subsystems 4 serial lines for subsyste...

Страница 47: ... C bus Optional module for supervising the NK822x power supply and detecting power failures and battery low conditions It is not needed when NK822x is installed in a fire or intrusion control unit whose power supply is already supervised NE8001 Wall mountable metallic cabinet with DIN rail including power supply unit Input 100 240 Vac Output 12Vdc 4A NE8002 Wall mountable metallic cabinet with DIN...

Страница 48: ...ystem and powered from the supervised power supply of the subsystem NK822x Ethernet Ports are supplied in a plastic box easy to install on DIN rails Alternatively the NK822x can be installed without the plastic box using the specific mounting kits for CS11 AlgoRex CS440 CS6 Guarto or SI410 420 Sintony Fig 21 NK822x mounting option for CS11 AlgoRex Fig 22 NK822x mounting option for CS6 Guarto Fig 2...

Страница 49: ...ne installations of NK822x are possible with the compact and convenient NE8001 and NE8002 housing solutions NE8001 includes a DIN rail power supply and DF8090 Power supply supervision module and is pre wired for a fast and easy installation of the NK822x NE8002 the empty enclosure including the mounted DIN rail Fig 24 NE8001 housing with installed NK822x and DF80xx modules ...

Страница 50: ...ASYS D100 Intrusion detection systems CS4 SI410 420 Sintony CS440 CZ12 Gas detection systems CC60 Video systems SIMATRIX video crossbar General I O systems CF9000 I O systems via IC 2 RS232 RS485 interface converter 3 rd party systems A number of 3 rd party systems are supported either via NK822x or MM8000 drivers For details see section 3 5 For network connectivity options see Appendix A 3 4 2 1 ...

Страница 51: ...9000 I O systems CF9003 DF8020 DF8040 DF8045 DF8046 mod ules Fig 26 Example of a subsystem connected via RS485 interface Note The serial interface COM1 can be configured either as RS232 or RS485 inter face This configuration requires hardware revision E or later 3 4 2 3 Subsystems connected via LON interface The following control units are supported Siemens CS6 Guarto intrusion detection systems u...

Страница 52: ...ted in a Cerloop configuration Fire detection systems CS11 AlgoRex CZ10 STT11 Système de Télécommande et Télésignalisation STT20 STT2410 Intrusion detection systems CS4 CS440 CZ12 Gas detection systems CC60 General I O systems MF7033 MM7033 digital PLC unit The Cerloop network is connected via the MK7022 to the NK8223 NK8225 Fig 28 Example of Cerloop network connected via MK7022 Note NK8223 NK8225...

Страница 53: ...e supported DF8090 Power supply supervision module max 1 module DF8020 8 output relays module max 1 module DF8040 8 input module max 2 modules 3 4 3 Parameterisation The NK8000 configuration is part of the Composer tool environment To perform the SW configuration for NK8000 market packages MP2 0 and later a WW8000 Com poser license is required The configuration tool includes connection parameters ...

Страница 54: ...evel configuration types Direct RS 232 NK8000 Direct LAN OPC connectivity client server Network components NK822x Control units MODBUS based systems CDDL CDSF based systems Fire detection systems Autronica BSxxx LIST SCU 2000 Intrusion detection systems MAXSYS PC6010 Gas detection systems CP100 Video systems Philips Burle Allegiant LTC 8x00 video switchers available in standard setup Geutebrück Mu...

Страница 55: ...o the NK8223 NK8225 for the centralisation of CF9000 I O System RS485 party lines for multiple units directly connected or via IC 2 converter CCTV SIMATRIX crossbar or Philips Burle Cerloop network via MK7022 CS11 AlgoRex CZ10 STT11 STT20 STT2410 Système de Télécommande et Télésignalisation CC60 Gas CS440 CS4 CZ12 intrusion control units and DMS7000 units Up to 4 CS6 Guarto units on the LON line S...

Страница 56: ...size systems are Universities Airports Amusement parks e g Disneyland Industries Pharmaceutical companies Hospitals Automobile manufacturing plants The following figure shows a typical campus site configuration The subsystems of each building are connected to an NK822x Ethernet Port The NK822x are connected via the LAN or WAN to the remote management station Fig 30 Example of NK822x connection to ...

Страница 57: ...ng figure shows a typical geographical network configuration The head quarters is equipped with several subsystems connected to an NK8223 NK8225 Ethernet Port The branches where a single fire or security subsystem needs to be centralised are equipped with NK8222 Ethernet Ports for a single subsystem The NK822x are connected via the LAN or WAN to the remote management station s Additionally dial up...

Страница 58: ...connected to NK822x and the lo cally connected I O modules Incoming messages can trigger one or more command messages to other subsystems Note Incoming messages can be combined with the logical operators AND OR XOR and NOT The configuration is done via an easy to use interactions tool and then downloaded to the NK822x Fig 32 Local interactions between subsystems connected to NK8223 NK8225 Fig 33 L...

Страница 59: ...al NK8000 I O DF80xx modules NK7022 Cerloop interface Philips Burle video switcher While the NK8225 is capable of the same local interactions as the NK8223 it is also capable of network wide interactions via BACnet IP to subsystems connected to other NK8225s Fig 34 Local and network wide interactions on NK8225 Limitations Network wide interactions on the NK8225 via BACnet IP are possible for the s...

Страница 60: ...ommend you use Cat 6 cable however which fulfils the specification for 100BaseTX networks Note The maximum length for an Ethernet segment for Ethernet 10BaseT and 100BaseTX is 100m 5 1 1 Repeater rules It is possible to extend the Ethernet length using repeaters hubs However you can not use infinite repeaters to extend the cable Note The transfer speed determines the number of repeaters you can in...

Страница 61: ... repeaters in serial star topology 100Mbps network For a 100Mbps network it is not possible to extend the line length with the 5 4 3 re peater rule This is due to the faster speed The maximum number of repeaters in serial for 100Mbps Ethernet is 2 5 1 2 Cable lengths Optimally you should use Cat 6 twisted pair cable Note The maximum cable length is 100 meters installed as follows 90 meters fixed i...

Страница 62: ... LANbooster 123 S D PW R A L 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 7 8 9 10 11 12 13 14 Uplink 1 00Base TX F DX 100B ase T X 13 14 A L F DX A L FDX 1 23 O N 15 LANbooster 123 S D Cisco 1720 BR I S T CO N SO L E AU X WI C 0 O K O K B 2 B 1 W IC 1 O K D S U CP U LN K 1 0 0 FD X S3 L O O P L P Field Field Field Field WAN Router Router Switch Switch Switch Repeater Hub 10BaseT 10BaseT 10BaseT 10BaseT...

Страница 63: ...es take place on fibre optic cables for OSM or TP ITP Twisted Pair Industrial Twisted Pair cables for ESM Redundant networks increase the overall security and reduce installation down times It is vital for safety and security applications that network reconfiguration time be as fast as possible after a network fault The extremely fast reaction times after detection ensure that a network can be rec...

Страница 64: ...C Optical Media Converters or directly via OSM Optical Switch Modules to the redundant network The total size of a network with Industrial Ethernet OSM can be up to 150km The maximum length for the fibre optic cable is 3 km with multimode fibre optic cable 26 km with single mode fibre optic cable You can find more information about Industrial Ethernet at http www siemens com industrial ethernet ...

Страница 65: ...types of information such as voice data LAN and video completely transparently throughout the network and does so with high availabil ity NETWORK It is based on fibre optic technology in a future proof network infrastructure spanning any distance An OTN network is built up with nodes that are interconnected by a dual fibre optic ring A network consists of up to 250 nodes Each node is mounted in a ...

Страница 66: ...he OTN network together with CCTV access control and telephony applications not shown in Fig 39 You can find more information about OTN at http www ic siemens be icn otn eng about shtm 5 3 Shared network It is possible to integrate FS NK8000 and management station products into a cus tomer s network however you need to be aware of satisfy the following require ments Only Ethernet is supported The ...

Страница 67: ...stomer should sign a contract that Siemens FS SES disclaims any liability for the customer s existing network Your customer will also need to know the following The IP address for each NK822x and each DMS PC tell where the devices are in stalled Redundancy network devices or paths available 5 3 2 Security and Application Port numbers Most companies use a Firewall or a Proxy server to protect the c...

Страница 68: ...g Bulletins Media Wiring 5 4 2 Serial interface RSxxx Transceiver Media Max Nodes per Segment Topol ogy Max Speed Connector Type Max Distance without spe cial HW Remarks URL RS 232 3 wires point to point PTP 115kbps D Sub 9 D Sub 25 RJ 45 15 Meter www phoenixcontact de www wut de RS 422 2 twisted pairs point to point PTP 1Mbps 1km speed distance trade off RS 485 master slave 1 twisted pair 32 depe...

Страница 69: ... 62 5 or 100 m 1024 per the whole network Star 10 Mbps ST SC or various connector Up to 2 km depending on the link budget 100BaseT 4 wire Copper cat 6 100 imped ance 1024 per the whole network Star 100 Mbps RJ 45 100 Meter Max 2 Re peaters in serial and the cable be tween the two repeaters max 5 meter 7 Switches in serial 100BaseT4 8 wire Cat 3 or better 100 imped ance 1024 per the whole network S...

Страница 70: ...ream 1 Mbps Upstream 128 kbps 5 4 km Proprietary technology from Rock well and Nortel HDSL 4 wire twisted pair 6 wire twisted pair Point to point Point to point 1 544 Mbps on two twisted pair lines 2 48 Mbps on three twisted pair lines 3 6 km T1 E1 service between server and phone com pany or within a company IDSL 2 wire telephone lines Point to point Point to point 128 kbps 5 4 km Similar to the ...

Страница 71: ...duct MM8000 MK8000 MT8001 and NK8000 a number of licenses ordering options are available Licenses needed depend on the system architecture and size For more details please consult the Details for ordering section in the product datasheet or contact your local sales distribution centre Be aware that actual calculations are available through the local sales channels ...

Страница 72: ...S DMS DMS MM MK MM MK MM MK MM MK MM MK MM MK STT11 DMS DMS MM MK MM MK MM MK STT20 MM MK MM MK MM MK STT2410 MM MK MM MK MM MK SIGMASYS D100 field test only MM MK MM MK MM MK MM MK CS440 DMS DMS DMS MM MK MM MK MM MK MM MK MM MK MM MK CS4 MM MK MM MK MM MK MM MK MM MK MM MK MM MK MM MK MM MK CZ12 MM MK MM MK MM MK MM MK MM MK MM MK MM MK MM MK MM MK CS6 Guarto via LON interface MM MK DMS MM MK MM...

Страница 73: ...ration Migration status Is the project a new system Yes No If no are there parts to be migrated to the new system Yes No Is this a replacement of an existing system Yes No If yes from which manufacturer Do you have existing SBT subsystems to be migrated Yes No If yes what type of subsystems 3 rd party integration Is it planned to integrate any 3 rd party subsystems Yes No If yes manufacturer and m...

Страница 74: ... a Management station connectivity How many management stations are foreseen Is a management level network foreseen interconnection of different man agement stations only Yes No If yes what type of management level network Ethernet Token Ring FDDI ATM etc b Management station to gateway connectivity Is a network planned to connect management station s and gateway s Yes No If yes what type of netwo...

Страница 75: ...ccessary Yes No If yes how IntERnet IntRAnet dial up Firewall configuration Are the necessary ports open TCP Port 3001 3004 NK822x TCP Port 20 FTP TCP Port 21 FTP UDP Port 47808 BACnet Yes Yes Yes Yes No No No No Availability Does the customer specify the network availability Yes No Are there special requirements regarding error failure rate Yes No If yes what are the requirements Is the power sup...

Страница 76: ...hnologies Group International Headquarters Fire Safety Security Products Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 Fax 41 41 724 35 22 www sbt siemens com Document no A6V10063710_a_en DMS8000 Sales Material Edition 06 2007 Section 4 ...