5
Siemens Schweiz AG
A6V11646020_en--_b
Smart Infrastructure
2020-07-10
Notes
Safety
CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and
property damage.
● Observe national provisions and comply with the appropriate safety regulations.
● This equipment is intended only for use in a restricted access area (lockable cabinet)
● This equipment is not suitable for use in locations where children are likely to be
present.
● Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply with the
requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS 60695-11-21.
Mounting position and ambient temperature
The devices can be snapped onto standard rails or screwed onto a flat surface.
Plug-in screw terminals connect power and interfaces.
Ambient temperature -5...50 °C (23...122 °F)
Ambient temperature -5...45 °C (23...113 °F)
● Wall, horizontal
–
From left to right
–
From right to left
● Overhead
● Wall, vertically
–
From top to bottom
–
From bottom to top
● On a horizontal surface
CAUTION
Risk of overheating for failure to comply with ambient temperature
Burning and damage to the device
● Ensure sufficient ventilation to comply with the permissible ambient temperature within
the panel or installation box. The temperature must be at least 10 K (18° F) lower
outside the installation box.
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.
● Dispose of empty batteries in designated collection points.