background image

    


Siemens Schweiz AG 

 

A6V11646020_en--_b 

Smart Infrastructure 

 

2020-07-10 

  

Conformity 

 

Ambient conditions and protection classification 
Classification as per EN 60730 
Automatic action 
Control function 
Degree of pollution 
Overvoltage category 

 
Type 1 
Class A 

III 

Design 

Suitable for use in protection class I or II systems 

Degree of protection of housing to EN 60529 
Front parts in DIN cut-out 
Terminal part 

 
IP30 
IP20 

Climatic ambient conditions 
●  Storage / Transport (packaged for transport) as per 

IEC EN 60721-3-2 

 

●  Operation as per IEC/EN 60721-3-3 
 

 
●  Class 1K22 / 2K21 

Temperature -25...70 °C (-13...158 °F) 

Air humidity 5...95 % (non-condensing) 

●  Class 3K22 

Temperature -5...50 °C (23...122 °F) 

 

(for details see chapter Mounting) 

Air humidity 5...95 % (non-condensing) 

Mechanical ambient conditions 
●  Transport per IEC/EN 60721-3-2 
●  Operation as per IEC/EN 60721-3-3 

 
●  Class 2M11 
●  Class 3M11 

 

 

 

Standards, directives and approvals 
Product standards 

EN 60730-1, EN 62368-1 

Product family standard 

EN 50491-x 

Electromagnetic compatibility (EMC) 

For residential, commercial, and 

industrial environments 

EU conformity (CE) 

See CE declaration 

1)

 

EAC compliance 

Eurasian compliance 

RCM conformity 

See RCM declaration 

1)

 

UL/cUL approbation (US / Canada) 

UL916; http://ul.com/database 

CSA certification 

C22.2, http://csagroup.org/services-industries/product-

listing 

FCC 

CFR 47 Part 15 Class B 

BACnet. 

B-BC 

Environmental compatibility 

1)

 

The product environmental declaration 

1)

 contains data 

on environmentally compatible product design and 

assessments (RoHS compliance, materials 

composition, packaging, environmental benefit, 

disposal).  

 

 

1)

 Documents can be downloaded at 

http://siemens.com/bt/download

. 

FCC Statement 
This equipment has been tested and found to comply with the limits for a Class B digital 

device, pursuant to part 15 of the FCC Rules. These limits are designed to provide 

reasonable protection against harmful interference in a residential installation. This 

equipment generates, uses and can radiate radio frequency energy and, if not installed and 

used in accordance with the instructions, may cause harmful interference to radio 

communications. However, there is no guarantee that interference will not occur in a 

particular installation. If this equipment does cause harmful interference to radio or television 

reception, which can be determined by turning the equipment off and on, the user is 

encouraged to try to correct the interference by one or more of the following measures: 
●  Reorient or relocate the receiving antenna. 
●  Increase the separation between the equipment and receiver. 

Содержание Desigo PXC5.E003

Страница 1: ...BACnet MS TP and Modbus devices Communication BACnet IP 2 port Ethernet switch for low cost cabling Integration of Modbus data points via RTU and or TCP Integration of BACnet MS TP devices WLAN interface for engineering and commissioning Operating voltage AC 24 V Mounted on standard rails or on the wall Plug in screw terminal blocks ...

Страница 2: ...et communication on IP or MS TP in compliance with the BACnet standard including B BC profile Rev 1 15 Wireless connection for engineering and commissioning Cloud connectivity for remote access Integration of Modbus data points via RTU and or TCP Type summary Type Order number Description PXC5 E003 S55375 C103 System controller to integrate up to 500 Modbus data points via RTU and or TCP up to 30 ...

Страница 3: ...using 14 Holes for wall mounting 2 Front cover 15 Date Series and Serial number 3 LEDs for communication and state 16 QR code for default WLAN access Description see Technical data LED displays Activity LED Color Activity Function Ethernet 1 2 Green Continuously ON Continuously OFF Flashing Link active No connection Network traffic Yellow Continuously ON Continuously OFF Link 100 Mbps Link 10 Mbps...

Страница 4: ... no client is connected As per description Do the following to reset the device to factory state 1 Power off the device 2 Power on the device 3 Wait until all LEDs light up and turn off again then press the Service button 4 Keep the Service button pressed until all LEDs light up then release the button All LEDs go off the device restarts 5 Wait until the device has fully started unconfigured green...

Страница 5: ... a flat surface Plug in screw terminals connect power and interfaces Ambient temperature 5 50 C 23 122 F Ambient temperature 5 45 C 23 113 F Wall horizontal From left to right From right to left Overhead Wall vertically From top to bottom From bottom to top On a horizontal surface CAUTION Risk of overheating for failure to comply with ambient temperature Burning and damage to the device Ensure suf...

Страница 6: ... GByte RAM 8 GByte eMMC Data backup in the event of power failure Energy reserve Supercap to support real time clock 7 days Energy reserve can be extended to min 1 month using optional battery CR2032 Battery safety requirement and specification for CR2032 according to IEC 60086 4 or UL1642 Battery must be rated for ambient temperature 70 C 158 F Data available if stored to flash memory Occurs ever...

Страница 7: ...hable with DIP switch Internal bus polarization 270 Ohm pull up pull down resistances switchable with DIP switch Cabling in house cabling only Distance between 2 devices Length of the MS TP line 3 wire cable shielded Max 500 m 1650 ft Max 1000 m 3300 ft Protection Short circuit proof Protection against faulty wiring with AC 24 V WLAN interface Interface type Wireless access point Supported standar...

Страница 8: ... UL cUL approbation US Canada UL916 http ul com database CSA certification C22 2 http csagroup org services industries product listing FCC CFR 47 Part 15 Class B BACnet B BC Environmental compatibility 1 The product environmental declaration 1 contains data on environmentally compatible product design and assessments RoHS compliance materials composition packaging environmental benefit disposal 1 ...

Страница 9: ...ion is subject to the following two conditions 1 This device may not cause interference and 2 this device must accept any interference received including interference that may cause undesired operation Radio frequency radiation exposure Information for USA and Canada This equipment complies with FCC and IC radiation exposure limits set forth for an uncontrolled environment This equipment should be...

Страница 10: ...nation Polar On off Switch for polarization 65 66 67 COM1 Interface EIA 485 Modbus MS TP 68 69 70 COM2 71 72 MBUS M bus interface for future use Warranty Technical data on specific applications are valid only together with Siemens products listed under Equipment combinations Siemens rejects any and all warranties in the event that third party products are used ...

Страница 11: ..._b Smart Infrastructure 2020 07 10 Dimensions All dimensions in mm and inches 124 4 88 117 4 61 110 4 33 129 5 08 4 1 0 1 6 144 5 67 26 5 1 04 45 1 77 65 5 2 58 70 5 2 78 4 0 16 21 5 0 85 11 0 43 45 1 77 21 5 0 85 11 0 43 35 5 1 40 49 1 91 ...

Страница 12: ...itzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice Document ID A6V11646020_en _b Edition 2020 07 10 ...