Siemens Desigo PXC5.E003 Скачать руководство пользователя страница 7

    

Siemens Schweiz AG 

 

A6V11646020_en--_b 

Smart Infrastructure 

 

2020-07-10 

Screw terminals, plug-in 
Stripping length 

6...7.5 mm (0.24...0.29 in) 

Screwdriver 

Slot screws, screwdriver size 1 

Max. tightening torque 

0.6 Nm (0.44 lb ft) 

 

 

 
The two COM interfaces can be used either for Modbus or for MS/TP, according to 

configuration. 

 

Modbus RTU interface 
Interface type 

EIA-485, electrically isolated  

Baud rate 

1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 

(depending on the configuration) 

Internal bus termination 

120 Ohm, switchable with DIP switch 

Internal bus polarization 

270 Ohm pull-up/pull-down resistances, switchable with 

DIP switch 

Cabling (in-house cabling only) 
Cable length 

3-wire cable 
Max. 1000 m (3300 ft) 

Protection 

Short-circuit proof  

Protection against faulty wiring with AC 24 V 

 

 

 

BACnet MS/TP interface 
Interface type 

EIA-485, electrically isolated  

Baud rate 

9600, 19200, 38400, 57600, 76800, 115200 (depending 

on the configuration) 

Internal bus termination 

120 Ohm, switchable with DIP switch 

Internal bus polarization 

270 Ohm pull-up/pull-down resistances, switchable with 

DIP switch 

Cabling (in-house cabling only) 
Distance between 2 devices 
Length of the MS/TP line 

3-wire cable, shielded 
Max. 500 m (1650 ft)  
Max. 1000 m (3300 ft) 

Protection 

Short-circuit proof 

Protection against faulty wiring with AC 24 V 

 

 

 

WLAN interface 
Interface type 

Wireless access point 

Supported standards 
Frequency band 
WLAN channels 
Maximum radio-frequency power 

IEEE 802.11b/g/n 
2.4…2.462 GHz 
1…11 
16.4 dBm 

Distance (unobstructed field) 

Min. 5 m (16 ft) 

Device pairing 

Activation / Deactivation with service button 
Automatic switch off after 10 minutes if no WLAN-client 

is connected. 
Optionally, for cyber security reasons, the WLAN can be 

permanently disabled via configuration. 

Default SSID and WLAN password: Scan the QR code.  

It will show something like WIFI:S:PXC5.E003_0000550;T:WPA;P:1400052738;;  

Then SSID = PXC5.E003_0000550 and password = 1400052738  
Determine manually: Use the information from the Date/Series/SN block It will show something like:  
Date/Series: 20190423A0000550  

S/N: 1400052738  
SSID = <ASN>_<Running number after the series letter> and password = <S/N>  

 

 

Содержание Desigo PXC5.E003

Страница 1: ...BACnet MS TP and Modbus devices Communication BACnet IP 2 port Ethernet switch for low cost cabling Integration of Modbus data points via RTU and or TCP Integration of BACnet MS TP devices WLAN interface for engineering and commissioning Operating voltage AC 24 V Mounted on standard rails or on the wall Plug in screw terminal blocks ...

Страница 2: ...et communication on IP or MS TP in compliance with the BACnet standard including B BC profile Rev 1 15 Wireless connection for engineering and commissioning Cloud connectivity for remote access Integration of Modbus data points via RTU and or TCP Type summary Type Order number Description PXC5 E003 S55375 C103 System controller to integrate up to 500 Modbus data points via RTU and or TCP up to 30 ...

Страница 3: ...using 14 Holes for wall mounting 2 Front cover 15 Date Series and Serial number 3 LEDs for communication and state 16 QR code for default WLAN access Description see Technical data LED displays Activity LED Color Activity Function Ethernet 1 2 Green Continuously ON Continuously OFF Flashing Link active No connection Network traffic Yellow Continuously ON Continuously OFF Link 100 Mbps Link 10 Mbps...

Страница 4: ... no client is connected As per description Do the following to reset the device to factory state 1 Power off the device 2 Power on the device 3 Wait until all LEDs light up and turn off again then press the Service button 4 Keep the Service button pressed until all LEDs light up then release the button All LEDs go off the device restarts 5 Wait until the device has fully started unconfigured green...

Страница 5: ... a flat surface Plug in screw terminals connect power and interfaces Ambient temperature 5 50 C 23 122 F Ambient temperature 5 45 C 23 113 F Wall horizontal From left to right From right to left Overhead Wall vertically From top to bottom From bottom to top On a horizontal surface CAUTION Risk of overheating for failure to comply with ambient temperature Burning and damage to the device Ensure suf...

Страница 6: ... GByte RAM 8 GByte eMMC Data backup in the event of power failure Energy reserve Supercap to support real time clock 7 days Energy reserve can be extended to min 1 month using optional battery CR2032 Battery safety requirement and specification for CR2032 according to IEC 60086 4 or UL1642 Battery must be rated for ambient temperature 70 C 158 F Data available if stored to flash memory Occurs ever...

Страница 7: ...hable with DIP switch Internal bus polarization 270 Ohm pull up pull down resistances switchable with DIP switch Cabling in house cabling only Distance between 2 devices Length of the MS TP line 3 wire cable shielded Max 500 m 1650 ft Max 1000 m 3300 ft Protection Short circuit proof Protection against faulty wiring with AC 24 V WLAN interface Interface type Wireless access point Supported standar...

Страница 8: ... UL cUL approbation US Canada UL916 http ul com database CSA certification C22 2 http csagroup org services industries product listing FCC CFR 47 Part 15 Class B BACnet B BC Environmental compatibility 1 The product environmental declaration 1 contains data on environmentally compatible product design and assessments RoHS compliance materials composition packaging environmental benefit disposal 1 ...

Страница 9: ...ion is subject to the following two conditions 1 This device may not cause interference and 2 this device must accept any interference received including interference that may cause undesired operation Radio frequency radiation exposure Information for USA and Canada This equipment complies with FCC and IC radiation exposure limits set forth for an uncontrolled environment This equipment should be...

Страница 10: ...nation Polar On off Switch for polarization 65 66 67 COM1 Interface EIA 485 Modbus MS TP 68 69 70 COM2 71 72 MBUS M bus interface for future use Warranty Technical data on specific applications are valid only together with Siemens products listed under Equipment combinations Siemens rejects any and all warranties in the event that third party products are used ...

Страница 11: ..._b Smart Infrastructure 2020 07 10 Dimensions All dimensions in mm and inches 124 4 88 117 4 61 110 4 33 129 5 08 4 1 0 1 6 144 5 67 26 5 1 04 45 1 77 65 5 2 58 70 5 2 78 4 0 16 21 5 0 85 11 0 43 45 1 77 21 5 0 85 11 0 43 35 5 1 40 49 1 91 ...

Страница 12: ...itzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice Document ID A6V11646020_en _b Edition 2020 07 10 ...

Отзывы: