Building Technologies
6 The settings in detail
2014-07-30
TRK Comfort
setpoint
TRR
Reduced room temperature setpoint
Tagem composite outside temperature
Overtemp prot pump heating circuit
Line no.
Operating line
HC1
HC2
HCP
820
1120
1420
Overtemp prot pump circuit
In the case of heating plant with pump heating circuits, the flow temperature of the
heating circuit can be higher than the flow temperature called for by the heating curve,
due to higher requests from other heat consumers (mixing heating circuit, DHW
charging, external heat demand), or a parameterized minimum heat pump temperature.
As a result of this too high flow temperature, the pump heating circuit would assume
excessive temperatures.
Function “Overtemperature protection for pump heating circuits” ensures that the
energy supply for pump heating circuits corresponds to the demand from the heating
curve by activating / deactivating the pump.
Mixing valve control
Line no.
Operating line
HC1
HC2
830
1130
Mixing valve boost
832
1132
Actuator type
2-position
3-position
833
1133
Switching differential 2-pos
834
1134
Actuator running time
Only with RVS13.143 and RVS53.183
For mixing, the actual value of the boiler flow temperature must be higher than the
required setpoint of the mixing valve flow temperature since otherwise that temperature
cannot be controlled. The controller generates the boiler temperature setpoint based on
the increase set here and the current flow temperature setpoint.
Selection of the type of actuator determines the way the control action impacts the type
of mixing valve actuator used.
For the 2-position actuator, the 2-position switching differential must also be adapted.
This is not required when using 3-position actuators.
Setting the actuator running time for the mixing valve used.
Floor curing function
Line no.
Operating line
HC1
HC2
HCP
850
1150
1450
Floor curing function
Off
Functional heating (Fh)
Curing heating (Bh)
Functional/curing heating
Curing heating/ functional heating
Manually
851
1151
1451
Floor curing setp manually
1455
Floor curing setp current
1456
Floor curing day current
Mixing valve boost
Actuator:type
Switching differential 2-
pos
actuator: running time