8 Technical data
2014-07-30
8.2 Extension module AVS75.390
Rated voltage
AC 230 V
(
±
10%)
Rated frequency
50 / 60 Hz
Max. power consumption
4 VA
External supply line protection
Fuse slow max. 10 A
…or
Circuit breaker max. 13 A
Characteristic B, C, D according to
EN 60898
(Power supply and outputs)
solid or stranded wire (twisted or with
ferrule):
1 core: 0.5...2.5 mm
2
2 cores 0.5...1.5 mm
2
Software class
A
Mode of operation to EN 60 730
1b (automatic operation)
Digital inputs H2
safety extra low-voltage for potentialfree
low-voltage contacts:
voltage with contact open: DC 12 V
current with contact closed: DC 3 mA
Analog input H2
protective extra low-voltage operating
range: DC (0...10) V
internal resistance: > 100 k
W
Mains input L
AC 230 V
(
±
10 %)
internal resistance: > 100 k
W
Sensor inputs BX6, BX7
NTC10k (QAZ36, QAD36)
Perm. sensor cables (copper)
with cross-sectional area:
Max. length
0.25 0.5 0.75 1.0 1.5 mm
2
20
40
60
80
120 m
Relay outputs
Rated current range
Max. switch-on current
Max. total current (of all relays)
Rated voltage range
AC 0.02…2 (2) A
15 A for
£
1 s
AC 6 A
AC (24...230) V (for potentialfree outputs)
External supply line protection
Refer to section "Power supply"
BSB
Max. cable length
Basic unit – peripheral device
Max. total length
Min. cross-sectional area
2-wire connection, not interchangeable
200 m
400 m (max. cable capacitance) 60 nF)
0.5 mm
2
Power supply
Wiring of terminals
Functional data
Inputs
Outputs
Interfaces