61/109
Siemens
User Manual
CE1U2357en
Building Technologies
6 The settings in detail
2014-07-30
Boost heating is used to reach the new setpoint more quickly when switching from the
Reduced setpoint to the Comfort setpoint, thus reducing the heating up time. During
boost heating, the room temperature setpoint is raised by the value set here.
A higher setting leads to shorter heating up times, a lower setting to longer heating up
times.
·
Boost heating is possible with or without room sensor.
TRw
Room temperature
setpoint
TRx
Actual value of the room temperature
DTRSA Increase of the room temperature setpoint
Quick setback
Line no.
Operating line
HC1
HC2
HCP
780
1080
1380
Quick setback
Off
Down to reduced setpoint
Down to frost prot setpoint
During quick setback, the heating circuit pump is deactivated and, in the case of mixing
circuits, the mixing valve is fully closed.
·
Function with room sensor:
When using the room sensor, the function keeps the heating switched off until the room
temperature has dropped to the level of the Reduced setpoint or the frost level.
When the room temperature has fallen to the Reduced level or the frost level, the
heating circuit pump will be activated and the mixing valve will be released.
·
Function without room sensor:
Quick setback switches the heating off for a certain period of time, depending on the
outside temperature and the building time constant.
Duration of quick setback when Comfort setpoint minus Reduced setpoint = 2 °C
(e.g. Comfort setpoint = 20 °C, Reduced setpoint =18 °C).
Outside
temperature
gemischt:
Building time constant:
0
2
5
10
15
20
50
15 °C
0
3.1
7.7
15.3
23
30.6
76.6
10 °C
0
1.3
3.3
6.7
10
13.4
33.5
5 °C
0
0.9
2.1
4.3
6.4
8.6
21.5
0 °C
0
0.6
1.6
3.2
4.7
6.3
15.8
-5 °C
0
0.5
1.3
2.5
3.8
5.0
12.5
-10 °C
0
0.4
1.0
2.1
3.1
4.1
10.3
-15 °C
0
0.4
0.9
1.8
2.6
3.5
8.8
-20 °C
0
0.3
0.8
1.5
2.3
3.1
7.7
Duration of quick setback in hours
Example
20
15
°C
t
TR
w
TR
x
2
3
7
1
D
0
3
DTRSA