44/109
Siemens
User Manual
CE1U2357en
Building Technologies
5 Handling
2014-07-30
O
p
e
ra
ti
n
g
lin
e
U
s
e
r
le
v
e
l
F
u
n
c
ti
o
n
D
e
fa
u
lt
v
a
lu
e
M
in
M
a
x
U
n
it
Heating circuit 2
1010 E Comfort
cooling
setpoint
20.0 BZ
1012
BZ 1016
°C
1012 E Reduced
setpoint
16
BZ 1014
BZ 1010
°C
1014 E Frost
protection
setpoint
10.0 4
BZ 1012
°C
1016 F Comfort
setpoint
max
35.0 BZ
1010
35
°C
1020 E Heating
curve slope
1.50 0.10
4.00
-
1021 F Heating
curve
displacement
0.0
-4.5
4.5
°C
1026 F Heating
curve
adaption
Off ¦ On
Off
-
1030 E Summer/winter heating limit
18
- - -
/ 8
30
°C
1032 F 24-hour
heating
limit
-3
- - -
/ -10
10
°C
1040 I
Flow temp setpoint min
8
8
BZ 1041
°C
1041 I
Flow temp setpoint max
80
BZ 1040
95
°C
1050 F Room
influence
20
- - -
/ 0
100
%
1060 F Room temp
limitation
1
- - -
/ 0.5
4
°C
1070 F Boost
heating
5
- - -
/ 0
20
°C
1080 F Quick
setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint
-
1090 F
Optimum start control max
0
0
360
min
1091 F
Optimum stop control max
0
0
360
min
1100 F
Reduced setp increase start
- - - - - -
/ -30
10
°C
1101 F
Reduced setp increase end
-15 -30
BZ 1100
°C
1120 F
Overtemp prot pump circuit
Off ¦ On
On
-
1130 F Mixing
valve
boost
10
0
50
°C
1132 F Actuator:type
2-position ¦ 3-position
3-position
-
1133 F Switching
differential
2-pos
2
0
20
°C
1134 F Actuator:
running
time
120 30
873
s
1150 I
Floor
curing
function
Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually
Off
-
1151 I
Floor
curing setp manually
25
0
95
°C
1160 F Recooling
storage
tank
Off ¦ Heating mode ¦ Always
Always
-
Heating circuit P
1300 E Operating
mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
Automatic
-
1310 E Comfort
cooling
setpoint
20.0 BZ
1012
BZ 1016
°C
1312 E Reduced
setpoint
16
BZ 1014
BZ 1010
°C
1314 E Frost
protection
setpoint
10.0 4
BZ 1012
°C
1316 F Comfort
setpoint
max
35.0 BZ
1010
35
°C
1320 E Heating
curve slope
1.50 0.10
4.00
-
1321 F Heating
curve
displacement
0.0 -4.5
4.5
°C
1326 F Heating
curve
adaption
Off ¦ On
Off
-
1330 E Summer/winter heating limit
18
- - -
/ 8
30
°C