background image

7XV5662-0AB01

English

C53000-B1174-C166-1

69

Housing

Dimensions

see figure 38 

Weight, approx. 

0.8 kg 

Degree of protection according 
to EN 60529

IP 41

Содержание 7XV5662-0AB01

Страница 1: ... Order No C53000 B1174 C166 1 Hinweise für den Einsatz Deutsch Seite 3 Kommunikationsumsetzer S0 Bus mit optischer asynchroner Eingangsschnittstelle Directions for use English page 37 Communication Converter S0 Bus with optical asynchronous input interface ...

Страница 2: ...NS AG Die übrigen Bezeichnungen in diesem Handbuch können Marken sein deren Benutzung durch Dritte für deren Zwecke die Rechte der Inhaber verletzen können Liability Statement We have checked the text of this manual against the hard ware and software described Exclusions and deviations cannot be ruled out we accept no liability for lack of total agreement The information in this manual is checked ...

Страница 3: ... 1 3 Inhalt Angaben zur Konformität 4 Hinweise und Warnungen 5 Aus und Einpacken des Gerätes 7 Lagerung 7 Verwendung 8 Merkmale 9 Funktion 10 Anschlüsse 11 Anschlusshinweise 12 Montage 15 Inbetriebsetzung 16 Technische Daten 32 Maßbilder 36 ...

Страница 4: ...trische Betriebsmittel zur Verwendung innerhalb bestimmter Spannungsgrenzen Niederspan nungsrichtlinie 73 23 EWG Diese Konformität ist das Ergebnis einer Prüfung die durch die Siemens AG gemäß Artikel 10 der Richtlinie in Übereinstimmung mit den Fachgrundnormen EN 50081 und EN 61000 6 2 für die EMV Richtlinie und der Norm EN 60255 6 für die Niederspannungs richtlinie durchgeführt worden ist Das Er...

Страница 5: ...tsmaßnahmen nicht getroffen werden Warnung bedeutet dass Tod schwere Körperverletzung oder erheblicher Sachschaden eintreten können wenn die entsprechenden Vorsichtsmaßnahmen nicht getroffen werden Vorsicht bedeutet dass eine leichte Körperverletzung oder ein Sachschaden eintreten kann wenn die entsprechenden Vorsichtsmaßnahmen nicht getroffen werden Dies gilt insbesondere auch für Schäden am oder...

Страница 6: ...eile dieser Geräte unter gefährlicher Spannung Es können deshalb schwe re Körperverletzung oder Sachschaden auftreten wenn nicht fachge recht gehandelt wird Nur entsprechend qualifiziertes Personal soll an diesem Gerät oder in dessen Nähe arbeiten Dieses muss gründlich mit allen Warnungen und Instandhaltungsmaßnahmen gemäß dieser Anleitung sowie mit den Sicherheitsvorschriften vertraut sein Der ei...

Страница 7: ...rgestellt werden Bevor das Gerät erstmalig oder nach Lagerung an Spannung gelegt wird soll es mindestens 2 Stunden im Betriebsraum gelegen haben um einen Temperaturausgleich zu schaffen und Feuchtigkeit und Betauung zu vermeiden Lagerung SIPROTEC Geräte sollen in trockenen und sauberen Räumen gelagert werden Für die Lagerung des Gerätes oder zugehöriger Ersatzbaugruppen gilt der Temperaturbereich ...

Страница 8: ...ichtungsvergleich bei Distanzschutz und Überstromzeitschutz zusammen mit dem Binärsignalübertrager 7XV5653 Der Anschluss an das Schutzgerät erfolgt störsicher über eine Lichtwellenleiter LWL Verbindung Dazu wird im Schutzgerät ein optisches 820 nm Steckmodul genutzt Weitere Informationen hierzu finden Sie im SIPROTEC Gerätehandbuch Der Datentransfer zwischen den Schutzgeräten stellt eine Punkt zu ...

Страница 9: ... dort integrierten FO Modul q Maximale LWL Länge für die Verbindung Schutzgerät KU S0 1 5 km mit 62 5 125 µm Multimodefasern Anschluss mit ST Stecker q 5 polige Schraubklemme S0 Bus Datenanschluss zum Kommunikationsgerät q Maximale Leitungslänge für die Verbindung Kommunikationsgerät NTBA KU S0 S0 Bus 150 m q Ein 9 poliger SUB D zum Anschluss an einen PC mit einem DIGSI Kabel 7XV5100 4 q Weitberei...

Страница 10: ...orzunehmen Die Anpassung erfolgt vollkommen bittransparent d h direktes Weiterleiten der Informationen ohne selbst Informationen hinzuzufügen oder auszublenden Bild 2 zeigt die Hardwarestruk tur Die Parametrierung des KU S0 s erfolgt über die PC Schnittstelle 9 poliger DSUB Stecker an der Gerätefront und dem KU S0 Konfigurationsprogramm FOS0 Configurator das unter http siemens siprotec de download...

Страница 11: ...er S0 Bus ist mit einem Abschlusswiderstand abgeschlossen Ein potentialfreier Kontaktausgang Relaiskontakt Wechsler dient zur Erzeugung des GOK Signals Gerät OK Signal Nur bei angezogenen Relais ist das Gerät zur Daten kommunikation bereit Der Öffner meldet eine Störung Alle Betriebszustände werden über LEDs signalisiert Anschlüsse Bild 3 Schnittstellen und Anschlüsse Auf der Geräteseite Bild 3 be...

Страница 12: ...rausgeführt sind Das Symbol am Anschluss stellt die Ruhelage des Kontaktes dar spannungslos Das GOK Signal wird aktiv Relais ist angezogen wenn die folgenden Bedingungen erfüllt sind n Power Fail Signal ist inaktiv internes Netzteil ist in Ordnung n RESET Signal ist inaktiv interne Logik ist in Ordnung n S0 Bus ist aufgelegt und funktionstüchtig q Stromversorgung Die Hilfsspannung ist an der 2 pol...

Страница 13: ...ermöglicht werden Bitte nur Kupferleiter verwenden Folgende Kabeltypen sind für den Anschluss zwischen NTBA und KU S0 zu verwenden Empfehlung Umgebung mit wenig bis keiner Störstrahlung J YY 2x2x0 6 StIII Bd Umgebung mit Störstrahlung J 2Y St Y 2x2x0 6 StIII Bd oder J Y St Y 2x2x0 6 StIII Bd Umgebung mit massiven Störern J YC St Y 2x2x0 6 StIII Bd Aus Tabelle 1 ist die Belegung für den Anschluss z...

Страница 14: ...iden Sie lassen sich durch eine Linksdrehung um 90 abnehmen Bild 6 LWL Anschlüsse für Sende und Empfangsrichtung LWL Stecker Typ ST Stecker zu verwendender Faser Typ Multimode LWL G62 5 125 µm empfohlen Wellenlänge λ ca 820 nm Zulässige Biegeradien für Innenkabel rmin 5 cm für Außenkabel rmin 20 cm Hinweis Die Klasse 1 nach EN 60825 1 wird bei Fasertyp G62 5 125 µm eingehalten PC Interface Pinbele...

Страница 15: ...ns jedoch 2 5 mm2 AWG 13 betragen q Anschluss des S0 Busses n Schließen Sie mittels Schraubendreher die beiden Adernpaare an den Anschluss S0 Bus des KU S0 s an Den verbleibenden Leiter Schirm schließen Sie an die Klemme S des Anschlusses an n Achten Sie unbedingt auf die korrekte Verdrahtung zwischen den Schnittstellen n Eine geschirmte Leitungen wird empfohlen siehe auch Anschlusshinweise q Verb...

Страница 16: ...Deckels lösen Konfiguration des KU S0 s Die Konfigurierung des KU S0 s geschieht über Steckbrücken Jumper Die in Tabelle 2 dargestellten Jumperpositionen entsprechen der Lieferstellung Busabschluss Ist der KU S0 letzter oder einziger Teilnehmer am S0 Bus sind die Jumper X22 und X25 auf die Stellung YES einzustellen Auslieferstellung bei dieser Einstellung wird der S0 Bus mit einem Widerstand von 1...

Страница 17: ...n Der Reset Taster darf nicht gedrückt sein n Der S0 Bus muss aufgelegt und funktionsfähig sein q LED 2 FO1 LWL1 Die erste gelbe LED FO1 LWL1 signalisiert durch blinken ob n Daten an der Receive Leitung des LWL1 anliegen und n zur Übertragung ein B Kanal freigegeben ist Somit kann beim Blinken dieser LED davon ausgegangen werden dass die am LWL1 Ein gang anliegenden Daten ins Kommunikationsnetz ge...

Страница 18: ...n die bestehenden Kommunikationsverbindungen unterbrochen Durch Betätigung des RESET Tasters werden alle Signalisierungselemente überprüft Parametrierung Der KU S0 kann mit dem Konfigurationsprogramm FOS0 Configurator oder einem Termi nal Programm z B Hyperterminal parametriert werden Zunächst soll die Parametrierung mit dem FOS0 Configurator beschrieben werden Parametrierung mit dem FOS0 Configur...

Страница 19: ...zum Beenden des Programms Bild 8 Mit dem Drop Down Menü wird die Auswahl aller beteiligen KU S0 s getroffen maximal 6 Mit dem nächsten Button dem grünen Haken können bei einer fertig parametrierten Konfiguration Plausibilitätsprüfungen durchgeführt werden Die Ergebnisse der Prüfungen werden im Fenster Meldungen s Bild 7 unten angezeigt Fehler bei der Prüfung werden in ROT und Warnungen in BLAU dar...

Страница 20: ... der grüne Pfeil auf dem Button wechselt zum Kreuz mit roter Farbe Bild 11 Parametrierungsdialog Beim Klick auf dem CFG Button Bild 11 wird ein Fenster geöffnet das dazu auffordert den RESET Knopf des KU S0 s zu betätigen Bei erfolgreicher Verbindungsaufnahme nach Betätigung des Buttons schließt sich das Fenster wieder automatisch Der KU S0 ist nun im Parametrier Modus und kann Daten vom PC empfan...

Страница 21: ...re Seite abhebt Wird bei einem KU S0 nur ein B Kanal benötigt und bleibt der andere somit frei sollte beim freien B Kanal im Feld own LWL1 2 FO1 2 ein Minuszeichen eingegeben werden somit wird bei der Prüfung dieser Kanal dann ignoriert In der unteren Buttonleiste des FOS0 Configurator Parametrierfeldes wird das zu ver wendende D Kanal Protokoll ausgewählt Bild 13 D Channel Protocol Zur Auswahl de...

Страница 22: ...l hier im Beispiel für die Wahlleitung DSS1 Bild 14 q Eintragung der eigenen Rufnummern für jedes LWL FO Pärchen im Eingabefeld own FO1 LWL1 Number bzw own FO2 LWL2 Number q Auswahl der Nummer der Gegenstelle im Drop Down Menü Number q Durch die Aktivierung von DIAL oder ACCEPT wird entschieden ob der KU S0 die Gegestelle rufen oder auf den Ruf der Gegenstelle warten und abheben soll q Durch den g...

Страница 23: ...XV5100 4 verbunden werden Im Fenster Datentransfer können die entsprechenden Befehle an den KU S0 während der Übertragung beobachtet werden Jeder Parametersatz für den KU S0 Berlin Hamburg oder Nürnberg muss in den jeweiligen KU S0 des Endes Berlin Hamburg oder Nürnberg übertragen werden Hinweis Wird bei einem KU S0 nur ein B Kanal benötigt und bleibt der andere somit frei sollte beim freien B Kan...

Страница 24: ...PT nicht notwendig Die Rufnummern werden von der Ver mittlungsstelle fest vergeben und automatisch angewählt Unmittelbar nach Anschluss des KU S0 s an den S0 Bus und entsprechender der Parametrierung wird die Verbindung aufgebaut und die Übertragung der Daten zu Gegenstelle kann beginnen Ferner ist das Durchschalten der Daten bei einer Standleitung fest vorgegeben und kann nicht beeinflusst werden...

Страница 25: ...eine Verbinden Sie PC und KU S0 mit der DIGSI Kommunikationsleitung 7XV5100 4 und starten Sie das Terminal Programm Nach Betätigung der RESET Taste des KU S0 s erfolgt folgende Ausschrift Nach dieser Ausschrift muss innerhalb der nächsten 3 Sekunden die Tasten CR CR ESC ESC betätigt werden um in den Konfigurationsmodus des KU S0 s zu gelangen Der erfolgreiche Start des Modus wird durch die Ausschr...

Страница 26: ... werden beide B Kanäle benutzt aciomco n Gibt an wieviele und welche unter aciomcatab1 und aciomcatab2 parametrierte Nummern nach einem Reset Power On gewählt werden sollen n 0 Es werden beide Nummern aciomcatab1 und aciomcatab2 gewählt n 1 Es wird nur die Nummer aciomcatab1 gewählt n 2 Es wird nur die Nummer aciomcatab2 gewählt n 3 Es wird keine Nummer gewählt aciomcatab1 Gibt die Nummer für den ...

Страница 27: ...enstelle warten Die Tabelle 4 zeigt eine mögliche Parametrierung Nach dem Start des Konfigurationsmodus mit dem Terminal Programm und der Eingabe des Kommandos show Tabelle 3 zeigt jeder KU S0 die folgende Ausschrift auf dem Terminal Umsetzer Kanal Rufnummer Wählen DIAL Rufannahme ACCEPT eigene Gegenstelle KU S0 1 Berlin B1 03012345 04012345 X B2 03067890 091167890 X KU S0 2 Hamburg B1 04012345 03...

Страница 28: ... 091167890 091167890 ist die zuwählende Nummer für das FO2 LWL2 Pärchen isdn 0 Setzt das ISDN Protokoll auf DSS1 Wahlleitung vmoddi 1 msni 03012345 Wird bei einem eingehenden Ruf die Nummer 03012345 angewählt werden die Daten zum FO1 LWL1 Pärchen durch geschaltet vmoddi 2 msni 03067890 Wird bei einem eingehenden Ruf die Nummer 03067890 angewählt werden die Daten zum FO2 LWL2 Pärchen durch geschalt...

Страница 29: ...abe des show Kommandos kann die Parametrie rung überprüft werden Die Parametrierungen der verbleibenden KU S0 s Hamburg und Nürnberg sind den Tabel len 6 und 7 zu entnehmen Kommando Kommentar defa 1 Setzt alle Parameter auf den Ausgangszustand aciomco 2 Es soll nur die unter aciomcatab1 parametrierte Nummer 03056789 nach dem RESET Power On gewählt werden Tabelle 6 Parametrierung des KU S0 2 Hambur...

Страница 30: ...tar defa 1 Setzt alle Parameter auf den Ausgangszustand aciomco 2 Es soll nur die unter aciomcatab2 parametrierte Nummer 03012345 nach dem RESET Power On gewählt werden aciomcatab1 04067890 04067890 ist die zu wählende Nummer für das FO1 LWL1 Pärchen aciomcatab2 03012345 03012345 ist die zu wählende Nummer für das FO2 LWL2 Pärchen isdn 0 Setzt das ISDN Protokoll auf DSS1 Wahlleitung vmoddi 1 msni ...

Страница 31: ...eweils verwendete B Kanal durch das Kommando aciomco x nach dem RESET Power On zu aktivieren ist hier im Beispiel aciomco 0 da beide B Kanäle benutzt werden sollen Kommando Kommentar defa 1 Setzt alle Parameter auf den Ausgangszustand aciomco 0 Es sollen beide B Kanal nach dem RESET Power On aktiviert werden isdn 14 Parametriert das zu verwendende ISDN Protokoll auf Stand leitung für beide B Kanäl...

Страница 32: ... 50 ms Wechselspannung Nennhilfswechselspannung UH 115 V bis 250 V 50 60 Hz zulässige Spannungsbereich 92 V bis 286 V Leistungsaufnahme ca 3 5 VA Lifekontakt GOK Kontakt 1 Wechsler Schaltleistung EIN 1000 W VA AUS 30 VA 40 W ohmisch Schaltspannung 250 V zulässiger Strom pro Kontakt 5 A dauernd 30 A für 0 5 s Schnittstelle zum Schutzgerät Lichtwellenleiter LWL LWL Stecker Typ ST Stecker optische We...

Страница 33: ...ntladung statischer Elektrizität IEC 60255 22 2 Klasse IV und IEC 61000 4 2 Klasse IV Bestrahlung mit HF Feld unmoduliert IEC 60255 22 3 Report Klasse III Bestrahlung mit HF Feld IEC 61000 4 3 Klasse III amplitudenmoduliert Bestrahlung mit HF Feld IEC 61000 4 3 ENV 50204 Klasse III pulsmoduliert schnelle transiente Störgrößen Burst IEC 60255 22 4 und IEC 61000 4 4 Klasse IV Energiereiche Stoßspann...

Страница 34: ...68 2 beim Transport Schwingung IEC 60255 21 1 Klasse 2 IEC 60068 2 6 Schock IEC 60255 21 2 Klasse 1 IEC 60068 2 27 Dauerschock IEC 60255 21 2 Klasse 1 IEC 60068 2 29 Temperaturen IEC 60068 2 empfohlene Temperatur bei Betrieb 5 C bis 55 C vorübergehend zulässige Grenztem 20 C bis 70 C peraturen bei Betrieb Grenztemperaturen bei Lagerung 25 C bis 55 C Grenztemperaturen bei Transport 25 C bis 70 C La...

Страница 35: ...7XV5662 0AB01 Deutsch C53000 B1174 C166 1 35 Gehäuse Abmessungen siehe Bild 19 Gewicht ca 0 8 kg Schutzart gemäß EN 60529 IP 41 ...

Страница 36: ...9 Abmessungen des Kommunikationsumsetzers n L 188 1 188 11 120 70 8 2 14 5 2 An der Wand montierte Hutschiene gehört nicht zum Lieferumfang Entriegelung 1 Hutschienenmindestlänge 2 Maßbild gilt für Hutschiene DIN EN 50022 35 x 7 5 Maße in mm Kreuzschlitzschraube ...

Страница 37: ...7 Contents Statement of Conformity 38 Notes and Warnings 39 Unpacking and Re packing 41 Storage 41 Application 42 Features 43 Function 44 Connections 45 Connection Instructions 46 Installation 49 Commissioning 50 Technical Data 66 Dimensions 70 ...

Страница 38: ...C and concerning electrical equipment for use within specified voltage limits Low voltage Directive 73 23 EEC This conformity has been proved by tests performed according to Article 10 of the Council Directive in agreement with the generic standards EN 50081 and EN 61000 6 2 for EMC directive and with the standards EN 60255 6 for low voltage directive by Siemens AG The product conforms with the in...

Страница 39: ... respective part of this booklet which is essential to highlight Warning Hazardous voltages are present in this electrical equipment during operation Non observance of the safety rules can result in severe personal injury or property damage Only qualified personnel shall work on and around this equipment after becoming thoroughly familiar with all warnings and safety notices of this booklet as wel...

Страница 40: ... operation of the equipment and the hazards involved In addition he has the following qualifications q Is trained and authorized to energize de energize clear ground and tag circuits and equipment in accordance with established safety practices q Is trained in the proper care and use of protective equipment in accordance with established safety practices q Is trained in rendering first aid ...

Страница 41: ... down in IEC 60255 21 1 class 2 and IEC 60255 21 2 class 1 Before initial energization with supply voltage or after storage the relay shall be situated in the operating area for at least two hours in order to ensure temperature equalization and to avoid humidity influences and condensation Storage SIPROTEC relays should be stored in dry and clean rooms The limit temperature range for storage of th...

Страница 42: ...tion and time overcurrent protection in combination with the binary signal transmitter 7XV5653 it is the permissive overreach tranfer trip or directional comparison pickup The connection to the protection device is made noise proof via a fibre optic link The fibre optic link means that this is an optical 820 nm plug in module in the protection device For more details see SIPROTEC device manual The...

Страница 43: ...re optic cable length for the connection between protection device CC S0 1 5 km 1 mile with 62 5 125 µm multi mode fibres Connection with ST connector q A 5 pole screw terminal is used for the data connection between the communication device DCE NTBA and CC S0 S0 Bus q Maximum line length for the connection between communication device DCE NTBA CC S0 150 m 450 ft q A 9 pole SUB D connector for the...

Страница 44: ...ion occurs completely bit transparent i e direct forwarding of the information without adding or filtering out information Figure 21 shows the hardware structure The parameter assignment of the CC S0 is done via the PC Interface RS 232 and the special configuration program FOS0 Configurator which can be downloaded from http siemens siprotec de download_neu ind_acc_e htm Alternative a simple Termin...

Страница 45: ...S0 Bus A contact output relay contact change over contact generates a device ready signal GOK DR Only when a relay has picked up the device is ready for data communication The NC contact signals a fault All operating states are signalled via LED s Connections Figure 22 Interfaces and connections The following interfaces and connections are located on the device side Figure 22 q S0 Bus The signals ...

Страница 46: ...ut on the device contact represents the life contact The symbol on the connection represents the contact s idle state Under the following conditions the DR Contact gets active n Power Fail signal is inactive internal power supply unit is in proper condition n RESET signal is inactive internal logic is in proper condition n The S0 Bus is connected and in service q Power supply The auxiliary voltage...

Страница 47: ...e 10 shows the connection between the NTBA and CC S0 The following listing shows usable cable types in deferent areas recommendation Areas with non or little EMC disturbance J YY 2x2x0 6 StIII Bd Areas with EMC disturbance J 2Y St Y 2x2x0 6 StIII Bd or J Y St Y 2x2x0 6 StIII Bd Areas with huge EMC disturbance J YC St Y 2x2x0 6 StIII Bd Voltage connections Direct connection Solid or stranded conduc...

Страница 48: ...t They can be removed by turning them 90 counter clockwise Figure 25 Fibre optic links for the transmission and reception directions FO connector type ST connector Necessary fibre type Multimode FO cable G62 5 125 µm recommended Wavelength λ approx 820 nm Perm bending radii for indoor cables rmin 5 cm 2 in for outdoor cables rmin 20 cm 8 in Note Class 1 as defined by EN 60825 1 is met in the case ...

Страница 49: ...section of the ground wire must be at least 2 5 mm2 AWG 13 q Connection of the S0 Bus interface n With a screwdriver connect the two core pair ends to the connection S0 Bus of the CC S0 Connect the remaining conductor shield to terminal S of the connection n It is essential to ensure that the wiring between the interfaces is correct n A shielded cable is recommended see also signal connection q Co...

Страница 50: ...mper settings If the CC S0 is the last or only device at the S0 Bus the jumpers X22 and X25 must set to the position YES delivery state At this jumper setting the S0 Bus is terminated with a 100 Ω resistance Table 11 Jumper for S0 Bus termination Settings in the protection device In the devices e g 7SD51 7XV5662 or 7XV5653 the asynchronous interface must be configured For devices with asynchronous...

Страница 51: ...el is ready for transmission A blinking LED 1 means that data is received from the FO1 input and the received data is routed though the CC S0 to the assigned B Channel It is not verified if the data reach the selected The LED light up if the RESET push button is pressed q LED 3 FO2 LWL2 The second yellow LED FO2 LWL2 signals via blinking that n data is received at the FO2 fibre optic input and n t...

Страница 52: ...ng chapters the parameter assignment with the FOS0 Configurator is described Parameter assignment with the FOS0 Configurator After the start of the FOS0 Configurators the program pops up with the following window figure 26 Figure 26 FOS0 Configurator The parameter assignment of the CC S0 takes place in two steps q The configuration of the constellation and q the download of the parameters into the...

Страница 53: ...S0 in constellation can be chosen The next button the green hook starts a plausibility check of the parameter of the constel lation The results of the plausibility test are shown in the message window see figure 26 below Errors are displayed in red and warnings are displayed in blue Figure 27 Main Menu FOS0 Configurator The CC S0 parameter assignment window figure 28 is similar to the printing on ...

Страница 54: ... and next three buttons are getting active figure 30 Now the parameter download dialog is active Figure 30 Parameter assignment dialog By clicking the CFG Button figure 30 a window pops up These window asks to press the RESET Button at the CC S0 After pressing the RESET Button at the CC S0 the window closes automatically The CC S0 is in the parameter assignment mode New parameter can be down or up...

Страница 55: ...can dial and the other CC S0 has to accept the incoming call So the parameter must be in opposite for one connection If one connection B Channel is not used type for the number The FOS0 Configurator ignores the channel the during the parameter check The last button field of the FOS0 Configurator the D Channel Protocol is assigned Figure 32 D Channel Protocol In drop down menu Fig 32 the D Channel ...

Страница 56: ...r every pair of fibre optic cables own FO1 LWL1 Number respectively own FO2 LWL2 Number q Assign the phone number of the partner device in the Drop Down Menu Number q Activate DIAL or ACCEPT for every CC S0 For every connection one CC S0 has to dial the other and the other CC S0 has accept the incoming call q Test the parameter assignment of the constellation by clicking the green hook in the Stan...

Страница 57: ...e parameter sets into different CC S0 s the PC Interface and CC S0 has to be connected with standard DIGSI communication cable 7XV5100 4 During the transmission all commands given by the FOS0 Configurator can be monitored in the Data Transfer Window Note If one connection B Channel is not used type for the number The FOS0 Configurator ignores the during the parameter check ...

Страница 58: ...re is no need to assign any number for the CC S0 Futhermore the choice of DIAL or ACCEPT is not necessary The communication link between the CC S0 s and the S0 Bus is established by the communication switch As far as the CC S0 s are connected to the S0 Bus the transmission starts In a leased line application any routing of the data is made by the communication switch The routing from the D channel...

Страница 59: ...lux control no Connect your PC via the DIGSI Communication cable 7XV5100 4 to CC S0 and start the terminal program on your PC After pressing the RESET Button CC S0 s answers on the terminal with To enter the configuration mode of the CC S0 press during the next three seconds CR CR ESC ESC on your PC Keyboard The successful entering of the configuration mode of the CC S0 is confirmed by the followi...

Страница 60: ...hed and which numbers are dialled after Reset or Power On n 0 both B Channels are established the dialled numbers are the number assigned at aciomcatab1 and aciomcatab2 n 1 only channel B is established the dialled number is the number which is assigned at aciomcatab1 n 2 only channel B is established the dialled number is the number which is assigned at aciomcatab2 n 3 no B Channel is established...

Страница 61: ...cepts the incoming call from his partner of the other end The following table 13 gives an overview of the constellation After the successful start of the configuration mode of the CC S0 the command show table 12 monitored the following printing at the terminal screen Converter Channel Numbers DIAL ACCEPT own number partner number CC S0 1 Berlin B1 03012345 04012345 X B2 03067890 091167890 X CC S0 ...

Страница 62: ...012345 04012345 is the dialled number for FO1 LWL1 aciomcatab2 091167890 091167890 is the dialled number for FO2 LWL2 isdn 0 sets the ISDN Protocol to DSS1 Dialling Line vmoddi 1 msni 03012345 If the an incoming call had dialled 03012345 the data are routed through FO1 LWL1 vmoddi 2 msni 03067890 If the an incoming call had dialled 03067890 the data are routed through FO2 LWL2 save save the assign...

Страница 63: ...he terminal via the show command The assignment of the CC S0 2 and CC S0 3 Hamburg and Nuremberg are listed in table 15 and 16 Command Description defa 1 resets all parameter to the state of delivery aciomco 2 only one B Channel starts dialling after Reset Power On or an interruption of the communication The dialled number is 03056789 assigned at aciomcatab1 Table 15 Parameter assignment CC S0 2 H...

Страница 64: ...Command Description defa 1 resets all parameter to the state of delivery aciomco 2 only one B Channel starts dialling after Reset Power On or an interruption of the communication The dialled number is 03012345 assigned at aciomcatab2 aciomcatab1 04067890 04067890 is the dialled number for FO1 LWL1 aciomcatab2 03012345 03012345 is the dialled number for FO2 LWL2 isdn 0 sets the ISDN Protocol to DSS...

Страница 65: ... is made by the communication switch The routing from the D channels to the fibre optic cables is also fixed The B1 channel is always routed to the FO1 LWL1 interface and the B2 channel is routed to FO2 LWL2 interface Command Description defa 1 resets all parameter to the state of delivery aciomco 0 both B Channel starts dialling after Reset Power On or an interruption of the communication isdn 14...

Страница 66: ...al power supply alternating voltage UH 115 V to 250 V 50 60 Hz Perm voltage range 92 V to 286 V Power input approx 3 5 VA Alarm relay GOK DR Contact 1 change over contact Switching capability MAKE 1000 W VA BREAK 30 VA 40 W resistive Switching voltage 250 V Permissible current per contact 5 A continuous 30 A for 0 5 s Interface to the protection device Optical fibre Fibre optic plug type ST plug O...

Страница 67: ...1 Class III and and VDE 0435 Part 303 Class III Static electricity discharge IEC 60255 22 2 Class IV and IEC 61000 4 2 Class IV Irradiation with HF field unmodulated IEC 60255 22 3 Report Class III Irradiation with HF field amplitude IEC 61 4 3 Class III modulated amplitude modulated Irradiation with HF field pulse IEC 61 4 3 Class III modulated pulse modulated Fast transient interference IEC 6025...

Страница 68: ...ss IEC 60255 21 and IEC 60068 2 During transport Vibration IEC 60255 21 1 Class 2 IEC 60068 2 6 Shock IEC 60255 21 2 Class 1 IEC 60068 2 27 Continuous shock IEC 60255 21 2 Class 1 IEC 60068 2 29 Temperatures IEC 60068 2 Recommended temperature during 5 C to 55 C operation Permissible temporary transient operating temperature 20 C to 70 C Limit temperatures during storage 25 C to 55 C Limit tempera...

Страница 69: ...7XV5662 0AB01 English C53000 B1174 C166 1 69 Housing Dimensions see figure 38 Weight approx 0 8 kg Degree of protection according to EN 60529 IP 41 ...

Страница 70: ... Converter n L 188 1 188 11 120 70 8 2 14 5 2 Mounting rails mounted on the wall are not included in the scope of delivery Unlocking 1 Minimum mounting rail length 2 The dimensioned drawing applies to the standard mounting rail DIN EN 50022 35 x 7 5 Dimensions in mm Cross recess screw ...

Страница 71: ...7XV5662 0AB01 C53000 B1174 C166 1 71 ...

Страница 72: ...ch zugestanden Zuwiderhandlungen ver pflichten zu Schadenersatz Alle Rechte für den Fall der Patenterteilung oder GM Eintragung vorbehalten Copying this document and giving it to others and the use or communication of the contents thereof are forbidden without express authority Offenders are liable to the pay ment of damages All Rights are reserved in the event of the grant of a patent or registra...

Отзывы: