Ones you have entered the configuration mode, the parameter of the CC–S
0
can be
assigned by some commands (see table 12).
Command
Description
show
shows the actual parameter assignment of the CC–S
0
on
terminal
save
saves the parameter into a resident memory
reset
resets the CC–S
0
defa 1
resets all parameters to the state as delivered
isdn x
assigns the D–Channel–Protocol:
x=0 dialling line (DSS1)
x=12 leased line for channel B1
x=13 leased line for channel B2
x=14 leased line for channel B1 and B2
aciomco n
assigns how many B–Channel has to be established and which
numbers are dialled after Reset or Power On:
n=0 both B–Channels are established, the dialled numbers
are the number assigned at aciomcatab1 and
aciomcatab2
n=1 only channel B is established, the dialled number is the
number which is assigned at aciomcatab1
n=2 only channel B is established, the dialled number is the
number which is assigned at aciomcatab2
n=3 no B–Channel is established
aciomcatab1
assigns the dialling number for FO1/LWL1 after Reset or
Power On
aciomcatab2
assigns the dialling number for FO2/LWL2 after Reset or
Power On
vmoddi/1.msni
assigns the number which is routed through the FO1/LWL1–
Connection by an incoming call.
vmoddi/2.msni
assigns the number which is routed through the FO2/LWL2–
Connection by an incoming call
Table 12: Terminal commands