7.2.2 RS232
It is possible to use an RS232 interface for installations where the distance between the master computer and the
inverters is less than 5 m and the amount of electrical interference generated by adjacent equipment is low.
For the connection method shown in Figure 9 below to operate satisfactorily, it is essential that there is no
connection between the 0V reference of the inverter (X11.1, X11.8, X11.10 or X11.22) and the ground reference for
the master computer.
RS232
TX
GND
INVERTER
A
B
X11
INVERTER
A B
X11
Figure 9: RS232 Connections
RX
TX = Pin 2
RX = Pin 3
GND = Pin 5 (Pin 7 for 25–way D–type connector)
A = X11.14
B = X11.15
100
Ω
7.3 Preparing the Inverter for Remote Control Operation
The inverter must be manually set into remote control mode before the remote control facility can be used. This is
achieved by programming configuration parameters P20, P21 and P22
(see section 5.3.2).
Parameter P20 selects manual/remote control and simple or USS protocol
When under manual control, the inverter will reply to query messages received over the serial link, but will
ignore commands to change its operational status. In remote control mode, all control is via the serial link.
All manual controls are ignored, except for the ability to switch back to manual mode by changing P20.
P20
= 000
Monitor mode, simple protocol
= 001
Control / Monitor mode, simple protocol
= 002
Monitor mode, USS protocol
= 003
Control / Monitor mode, USS protocol
Parameter P21 selects the device number (0 to 30)
Each inverter connected to the serial line must be allocated a unique device number. This is used to
identify which inverter the remote device wishes to talk to. Each inverter will only respond to commands
destined for that inverter.
P21 = appropriate address (000 to 030)
Parameter P22 selects the serial baud rate and parity
The inverter will operate at 2400, 4800 or 9600 baud with even, odd or parity ignored.
P22
= 000
2400 baud
even parity
= 001
4800 baud
even parity
= 002
9600 baud
even parity
= 003
2400 baud
odd parity
= 004
4800 baud
odd parity
= 005
9600 baud
odd parity
= 006
2400 baud
ignore
= 007
4800 baud
ignore
= 008
9600 baud
ignore
Содержание 6SE2101-1AA01
Страница 5: ...English vi Siemens plc 1993 This page intentionally blank ...
Страница 11: ...English 2 2 Siemens plc 1993 This page intentionally blank ...
Страница 53: ...English 7 18 Siemens plc 1993 This page intentionally blank ...
Страница 59: ...Deutsch vi Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Страница 65: ...Deutsch 2 2 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Страница 107: ...Deutsch 7 18 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...