POWER TERMINALS: TERMINAL BLOCK X1
Single Phase Input Units:
Connection
Terminal
Labelling
Function, Data, Notes
U1
X1.L1
Mains
N1
X1.N
PE
X1.
Ground
PE
X1.
Ground
U2
V2
W2
X1.U
X1.V
X1.W
Motor connection
3AC 0 V... Line voltage
0.0 ... 400 Hz
M
3
Three Phase Input Units:
U1
X1.L1
V1
W1
PE
X1.L2
X1.L3
X1.
Ground
Mains connection
3AC 380 – 500 V +/–10%
50/60 Hz
PE
X1.
Ground
U2
V2
W2
X1.U
X1.V
X1.W
Motor connection
0.0 ... 400 Hz
M
CONTROL TERMINALS: TERMINAL BLOCK X11
X11.1
X11.2
X11.3
X11.4
X11.5
X11.6
X11.7
X11.8
X11.9
X11.10
X11.11
X11.12
=
+
24 V
0 V
100 k connection to ground
Run/Stop
Level or edge–triggered (P05)
+15 V
Forward/Reverse
Closed = reverse
+10 V Ref.
Reference voltage for potentiometer
0...10 V
Frequency set–point (voltage) (P04)
0 V
0 (4)...20 mA
Frequency set–point (current) (P04)
0 V
0...10 V/5 mA
Frequency/Output current indication
0...50 V
Tachometer input
1AC 220 – 240 V +/–10% 50/60 Hz
5 k
=
+
–
Tacho
3
Figure 3: Connection Diagram
X11.13
Jog
Jog speed set by parameter P12
Ω
DC – Output
X1.–
Connections for Braking Module
DC + Output
X1.+
Trip
Can be used in conjunction with Run/Stop
and with PTC.
X11.14
X11.15
X11.16
X11.17
A
RS485 Serial I/O connection
B
‘P’ Button connection
‘ ’ Button connection
X11.18
‘ ’ Button connection
X11.2
X11.19
X11.20
X11.21
X11.22
NO
Fault indication
COM
NC
0 V
(energised during normal operation)
3AC 0 V... Line voltage
X11.2
Содержание 6SE2101-1AA01
Страница 5: ...English vi Siemens plc 1993 This page intentionally blank ...
Страница 11: ...English 2 2 Siemens plc 1993 This page intentionally blank ...
Страница 53: ...English 7 18 Siemens plc 1993 This page intentionally blank ...
Страница 59: ...Deutsch vi Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Страница 65: ...Deutsch 2 2 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Страница 107: ...Deutsch 7 18 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...