7.5.3 Message Structure – Inverter to Control Device
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
PKE High
PKE Low
Parameter Number
Always 0
Parameterisation Status
0 0 0 0
0 0 0 1
0 1 1 1
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
PZD1 High
PZD1 Low
‘READY FOR
‘FAULT’
‘OFF3 NOT AVAILABLE’
‘OFF2 AVAILABLE’
‘SWITCH ON
‘NO ALARM’
Always 1
‘READY’
Always 1
‘OPERATION
0 Stopped
1 Running / Jog
0 No Fault
1 Inverter Tripped
Always 1
Always 0
0 Switch On Inhibit Cleared
1 Inverter in Switch On Inhibit State
Always 0
‘WITHIN TOLERANCE’
Always 1
‘AUTOMATION CONTROL’
0 Serial Control Locked Out
1 Control by Automation Device
‘FORWARD’
0 No Meaning
1 Forward
‘REVERSE’
0 No Meaning
1 Reverse
Unused
‘READ CURRENT’
0 PZD2 Returns Frequency
1 PZD2 Returns Current
(spontaneous reports not supported)
No task performed
Parameter value in PWE
Error code in PWE
PWE = 0 – Invalid parameter number
PWE = 101 – Function not implemented
1 0 0 0
Parameter write not permitted
SWITCH ON’
ENABLED’
INHIBIT’
‘SETPOINT REACHED’
0 Output Frequency Below Set–point
1 Set–point Reached or Exceeded
Содержание 6SE2101-1AA01
Страница 5: ...English vi Siemens plc 1993 This page intentionally blank ...
Страница 11: ...English 2 2 Siemens plc 1993 This page intentionally blank ...
Страница 53: ...English 7 18 Siemens plc 1993 This page intentionally blank ...
Страница 59: ...Deutsch vi Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Страница 65: ...Deutsch 2 2 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...
Страница 107: ...Deutsch 7 18 Siemens plc 1993 Diese Seite bleibt absichtlich frei ...