7.5.1.13 Automation Control
When AUTOMATION CONTROL (PZD1 bit 10) is set to 0 in a command message, the inverter will not action serial
commands until a message is sent with this bit set to 1.
7.5.1.14 Spontaneous Reports
Bit 11 of PKE is used to indicate spontaneous reports in the USS protocol. Such reports are initiated by the inverter
in response to an internal event – such as a trip, or a threshold being reached.
These reports are not supported by the 6SE21. This bit is always set to 0 in reply messages.
7.5.1.15 Reply Message PZD1 Status Bits
The reply bits OPERATION ENABLED, ON LEFT, ON RIGHT, FAULT, OFF2 AVAILABLE, OFF3 AVAILABLE,
SWITCH ON INHIBIT, AUTOMATION CONTROL and SETPOINT REACHED have already been described in the
preceding sections.
In addition, the following status bits are transmitted:
READY FOR SWITCH ON
Bit 0
Always set to 1.
READY
Bit 1
Always set to 1.
ALARM
Bit 7
Always set to 0.
WITHIN TOLERANCE
Bit 8
Always set to 1.
UNUSED BITS
Bits 13 & 14
Always set to 0.