Setting for device
②
and
④
Redundant HSR PRP coupling, LAN B (The port P1/A is open and must not be used.)
Configuration of the "NetID" parameter
The network ID of the PRP network is specified with this parameter. The valid range of values is
1 to 6. The devices SCALANCE X204RNA
①
and
②
belong to the same PRP network and you
therefore need to set the same value for the NetID parameter for both devices. The same applies
to the devices SCALANCE X204RNA
③
and
④
. The last devices named belong however to a
different PRP network and for this reason a different NetID from the devices
①
and
②
must be
used. For example NetID "5" could be assigned for devices
①
und
②
and NetID "6" for devices
③
and
④
.
Network topologies and redundancy
4.3 HSR-PRP coupling
SCALANCE X-200RNA
Operating Instructions, 04/2022, C79000-G8976-C342-07
29