Instructions for fitting connectors, attachments and devices
2.3 Electrical networks
Passive network components
System Manual, 02/2013, C79000-G8976-C282-01
33
2.3.8
Fitting the IE FC TP standard cable 4 x 2 GP to an IE IP 67 hybrid connector
Introduction
The individual steps required to assemble an IE FC TP standard cable 4x2 and an IE IP67
hybrid plug are explained below.
Note the information in the compact installation instructions of the SCALANCE W700
devices.
Procedure
Remove the two inner shells of the universal sealing ring
to adapt it to the diameter of the hybrid cable.
Push the bushing, washer, adapted universal sealing
ring and the housing over the cable jacket.
Remove the following lengths of cable jacket and shield
braid:
25 mm
30 mm
25 mm for the power leads
30 mm for the data leads
To achieve good shielding, the shield braid must be alt
least 30 mm long.