SR882 operation manual
~ 27 ~
Setup the switch-on temperature difference:
Under standby status, access main menu DT,
►Press “SET” button, to access settings program of
DT, “DT 1o 08
℃
” displays on the screen, “08
℃
” blinks,
the switch-on temperature difference can be set.
►Press “+”“-” button, to adjust the value of switch-on
DT, adjustable range (OFF+2
℃)~
20
℃,
factory setting
is 8
℃
►Press “ESC” button to confirm the DT 1o set point.
►Press “+” button, “DT 1F 04
℃
” displays on the
screen
►Press “SET” button, “04
℃
” blinks, the switch-off
temperature difference can be set.
►Press “+”“-” button to adjust the value of switch-off DT, adjustable range 0
℃~(
ON-2
℃),
factory set is 4
℃
.
►Press “ESC” to exit menu, or wait for 20 seconds to exit automatically, the setup
parameters are saved automatically.
4.3 TEMP Temperature
For every system, the factory set parameters are in the best condition that is fully integrated
into the entire solar system. But these parameters can also be set individually to cater the
special requirements, please carefully observe the operation data of system components
after setting.
Note:
parameters that can be set depend on the system design, not all the parameters can
be adjusted in a solar system.