Average value: Holds the mathematical average of all measured values present in
the interval between the last falling edge and the hold input signal (next rising
edge).
ON
OFF
1
2
3
HOLD
1
Measured value
2
Output hold value (average hold value)
3
Interval in which an analysis is carried out.
8.4.3.1.3
Teach-in
Description
In the
Teach-in
operating mode you can use various teach functions by creating signal
levels of various lengths at the In1 input.
The timing tolerance for all teach functions is +/- 20 ms.
The following functions are available:
Teach function
Time [ms]
Switching off laser
200
Switching on laser
300
Distance to object for Q
1
: Teach Q
400
Distance to object for Q
1
: Teach Q not
500
Switching window for Q
1
: Teach Q near
600
Switching window for Q
1
: Teach Q far
700
ObSB (Background) for Q
1
: Teach Q
800
ObSB (Background) for Q
1
: Teach Q not
900
Switching window for Q
1
: Centering teach
1000
Distance to object for Q
2
: Teach Q
1100
Distance to object for Q
2
: Teach Q not
1200
Switching window for Q
2
: Teach Q near
1300
Switching window for Q
2
: Teach Q far
1400
ObSB (Background) for Q
2
: Teach Q
1500
ObSB (Background) for Q
2
: Teach Q not
1600
Switching window for Q
2
: Centering teach
1700
Q
A
with 4-20 mA for Q
2
: Teach 4 mA
1800
Q
A
with 4-20 mA for Q
2
: Teach 20 mA
1900
Q
A
with 0-10 V for Q
2
: Teach 0 V
2000
Q
A
with 0-10 V for Q
2
: Teach 10 V
2100
Q
A
(4-20 mA or 0-10 V): Centering teach
2200
Switching off teach confirmation
2300
8
OPERATION VIA DISPLAY
50
O P E R A T I N G I N S T R U C T I O N S | OD1000
8019642/18JN/2020-07-01 | SICK
Subject to change without notice