38
3. Primary operation
Primary operation
Steps
Description
1
Note: 1. When P.79=0, after the power is turned on or the inverter is reset, press
MODE
to shift to
‘operating mode’. The inverter will enter the external mode first, then press
or
to
shift to PU mode.
2. When P.79=2, the inverter will always in external mode.
3. For selection and shifting of operation modes, please refer to Section 3.1.
2
• If the target frequency is set by the input signal across terminal 4-5, please refer to P.39 in
Chapter 4.
• If the target frequency is set by multi-speed stage levels, please refer to P.4 in Chapter 4.
• If the target frequency is set by the input signal across terminal 2-5, please refer to P.38 in
Chapter 4.
• If programmable operating mode is chosen, please refer to multi-function terminals
P.80~P.84
、
P.86 in Chapter 4.
3
• Turn on STF or STR, the motor will run.
• At this time, the indicating lamp of
will flicker which indicates that the motor is
running.
Note: 1. For advanced setting of the starting terminals STF and STR, please refer to P.78 and
multi-function terminal P.80~P.84
、
P.86 in Chapter 4.
2. For the operating procedure of the monitoring mode, please refer to Section 3.2.
3. If programmed operation mode is chosen, STF becomes starting signal and STR becomes pause
signal, they are not Run Forward or Run Reverse terminals anymore.
4
• Turn off STF or STR, and the motor will decelerate till it stops.
• The indicating lamp of
will not turn off until the inverter has stopped putting out
voltages.
3.5 The basic operation procedure for JOG mode (
, Pr79=0 or 1)
Steps
Description
1
• Change the operation mode to the JOG mode; and the indicating lamp of
will be
lit, and the screen will display
before the motor runs.
Note: For selection and shifting of the operation modes, please refer to Section 3.1.
2
• Press down
FWD
or
REV
, then the motor will run. At this time, the indicating lamp of
will flicker which indicates that the motor is running.
• When releasing
FWD
or
REV
, the motor will decelerate, till it stops. The indicating lamp
will not turn off until the motor has stopped putting out voltages.
Note: 1. For the operating procedure of the monitoring mode, please refer to Section 3.2.
2. In the JOG mode, the target frequency is the value of P.15, and the acceleration/deceleration
time is the value of P.16. Please refer to Pr.15 in Chapter 4.