25
2.
Introduction of Shihlin Inverter
Introduction of Inverter
2.7.2 Power cable specification/pressing connection terminals specification
Inverter type
Power cable specification
Pressing connection terminal
specification (used by power cables)
Cables for the
power supply
R.S.T (mm
2
)
Cables for the
output U.V.W
(mm
2
)
Cables for the
power supply
R.S.T (mm
2
)
Cables for the
output U.V.W
(mm
2
)
SE2-021-0.4K
2
2
2 - 4
2 - 4
SE2-021-0.75K
2
2
2 - 4
2 - 4
SE2-021-1.5K
2
2
2 - 4
2 - 4
SE2-021-2.2K
3.5
3.5
5.5 - 4
5.5 - 4
SE2-023-0.4K
2
2
2 - 4
2 - 4
SE2-023-0.75K
2
2
2 - 4
2 - 4
SE2-023-1.5K
2
2
2 - 4
2 - 4
SE2-023-2.2K
2
2
2 - 4
2 - 4
SE2-023-3.7K
3.5
3.5
5.5 - 4
5.5 - 4
SE2-023-5.5K
5.5
5.5
5.5 - 5
5.5 - 5
SE2-023-7.5K
14
8
14.5 - 5
8 - 5
SE2-043-0.4K
2
2
2 - 4
2 - 4
SE2-043-0.75K
2
2
2 - 4
2 - 4
SE2-043-1.5K
2
2
2 - 4
2 - 4
SE2-043-2.2K
2
2
2 - 4
2 - 4
SE2-043-3.7K
2
2
2 - 4
2 - 4
SE2-043-5.5K
3.5
2
5.5 - 4
2 - 4
SE2-043-7.5K
3.5
3.5
5.5 - 4
5.5 - 4
SE2-043-11K
5.5
5.5
5.5 - 5
5.5 - 5