71
4. Parameter description
Parameter
●
Communications examples
Example 1
.
Write CU (communication) mode by Communication
Step 1.PC to modify the inverter mode
Mode
Start
Address
Function
Initial address
Write data
Check
End
ASCII
H3A
H30 H31
H30 H36
H31H30 H30 H30 H30 H30 H30 H30 H45 H39
0D 0A
RTU
>=10ms
01
06
10
00
00
00
8D 0A
>=10ms
Step 2.After receiving and processing accurate, the inverter responsed PC
Mode
Start
Address
Function
Initial address
Write data
Check
End
ASCII
H3A
H30 H31
H30 H36
H31H30 H30 H30 H30 H30 H30 H30 H45 H39
0D 0A
RTU
>=10ms
01
06
10
00
00
00
8D 0A
>=10ms
Example 2
.
PC communication to read P.195:
Step 1.PC requests the inverter to read the value of P.195. The address of P.195 is H00C3
。
Mode
Start
Address
Function
Initial address
Register number
Check
End
ASCII
H3A
H30 H31
H30 H33
H30H30 H43 H33 H30 H30 H30 H31 H33 H38
0D 0A
RTU
>=10ms
01
03
00
C3
00
01
74 36
>=10ms
Step 2.After inverter receives the information and processes without error; it sends value of P.195 to
PC.
Mode
Start
Address
Function
Read data number
Read data
Check
End
ASCII
H3A
H30 H31
H30 H33
H30 H32
H31 H37 H37 H30 H37 H33
0D 0A
RTU
>=10ms
01
03
02
17
70
B6 50
>=10ms
H1770 into decimal is 6000, the unit of P.195 is 0.01
,
so 6000×0.01
=
60
,
60 is the valueof P.195.
Example 3
.
Change value of P.195 to 50
Step 1.PC requests the inverter to inputting 50 into P.195.
Mode
Start
Address
Function
Initial address
Write data
Check
End
ASCII
H3A
H30 H31
H30 H36
H30H30
H43 H33
H31 H33
H38 H38
H39 H42
0D 0A
RTU
>=10ms
01
06
00
C3
13
88
74 A0
>=10ms
Step 2.After receiving and processing accurate, the inverter responsed PC
Mode
Start
Address
Function
Initial address
Write data
Check
End
ASCII
H3A
H30 H31
H30 H36
H30H30
H43 H33
H31 H33
H38 H38
H39 H42
0D 0A
RTU
>=10ms
01
06
00
C3
13
88
74 A0
>=10ms