Parameter Description
Parameter Description
95
5.28 Remote Control Function Selection (P.61)
P.61 “Remote setting function selection”
● If the operation box is located away from the control box, contact signals can be used to perform
the continuous variable-speed operation without using analog signals at the external mode, the PU
mode, the combined mode 1 or the combined mode 5.
Parameter
Factory
Setting
Setting
Range
Remarks
Set
Value
Remote Set
Function
Frequency Setting Storage Function
61
0
0~3
0
No
---
1
Yes
Yes
2
No
3
No
(The remote setting frequency is cleared
by turning off STF/STR.)
<Setting>
• Remote setting function
1. Whether the remote setting function is valid and whether the frequency setting storage function in
the remote setting mode is used is selected by P.61.
Set P.61=1~3 (remote setting function is valid), the function of terminals RM, RH and RL are
changed to acceleration (RH), deceleration (RM) and clear (RL). As shown in the following
Figure:
Wiring of remote control setting
Содержание SS2 Series
Страница 21: ...Introduction of Shihlin Inverter Introduction of Inverter 17 3 5 5 System wire arrangement ...
Страница 174: ...Appendix 6 European Specification Compatibility Description Specification Description 170 CE Certification Statement ...