Parameter Description
Parameter Description
80
5.18 Speed Display (P.37, P.259)
P.37 “Speed display”
P.259 “Speed unit selection”
● At the output frequency monitoring mode, the screen will display the corresponding mechanical
speed.
Parameter Factory Setting
Setting Range
Remarks
37
0 r/min
0~5000.0r/min
0
Output frequency
0.1~5000.0r/min P.259=1
0~9999 r/min
1~9999 r/min
P.259=0
259
1
0, 1
---
<Setting>
• The set value of P.37 is the mechanical speed of the inverter when its output frequency is 60Hz. If
P.37 is needed to be set to 9999, please set P.259 to 0 before setting P.37.
For example: If the transmitting belt speed is 950 m/minute when the inverter output frequency is
60Hz, P.37 shall be set to 950. At the output frequency monitoring mode, the screen
will display the speed of the transmitting belt.
Note: 1. There maybe are discrepancies (in minutes) between the displayed mechanical speed and the actual one.
2. Please refer to Section 4.1 for detailed operation for the operation panel working mode.
3. When P.259=0 and the output mechanical speed is more than 9998, the screen will display 9999, and the
maximum speed of inverter won’t exceed 65535; when P.259=1 and the output speed is more than 999.9,
the screen will only display the part of intger number, and the maximum speed of inverter won’t exceed
6553.5
Содержание SS2 Series
Страница 21: ...Introduction of Shihlin Inverter Introduction of Inverter 17 3 5 5 System wire arrangement ...
Страница 174: ...Appendix 6 European Specification Compatibility Description Specification Description 170 CE Certification Statement ...
Страница 175: ...Appendix 6 European Specification Compatibility Description Specification Description 171 ...