Introduction of Shihlin Inverter
Introduction of Inverter
12
3.5 Installation and Wiring
3.5.1 Transport
Take the pedestal when carrying and don’t only take the cover or any part of the inverter,
otherwise it may drop down.
3.5.2 Stockpile
This product before installing must be placed in the packaging. If it is not in use, change the
frequency to meet the company's warranty scope and future maintenance. Pay attention to the
following matters for storage:
1.
Must be placed in dry and without dirt place.
2. The environment temperature for storage position must range from -20
℃
to +65
℃
.
3. The relative humidity for storage position must range from 0% to 95%, and no condensation.
4. Avoid storing in the environment which contains corrosion gas or liquid.
5. It had better be packed properly and kept on shelf or table.
Note: 1. Even if the humidity meets the standard requirements, icing and condensation can also occur when the
temperature changes rapidly. And the place should avoid.
2. Don't place it on the ground, and it should be placed on appropriate shelf. If in the bad surroundings, the
desiccant should be placed in the packaging bag.
3. If the custody period is more than 3 months, the ambient temperature should not be higher than 30
℃
. It is
to consider that the character will easily degrade in high temperature when the electrolytic capacitors are
deposited without electricity.
4. If the inverter is installed in device or control board when not in use (especially in construction site or the
humid and dusty place), the inverter should be removed and put in suitable environment according with
the above storage conditions.
5. If the electrolytic capacitors are long-term no electricity, the character will degrade. Do not place it in the
state of no electricity for more than one year.
3.5.3 EMC Installation instructions
Inverter is similar to other electrical and electronic equipments. In a power system, an inverter is
the electromagnetic interference
source and also the electromagnetic receiver. The working principle
of inverter determines that it will produce certain electromagnetic interference noise. In order to
guarantee the inverter working reliably in the electromagnetic environment, it must have a certain
abilitily of anti-electromagnetic interference in design. In order to make the drive system work
normaly, and meet
CE declared requirements, please meet the following several aspects requirements
in installation:
1. Field wiring
Power line supply electric independently from power transformer, five core or four core line are
generally used, null line and ground sharing a single line is forbidden.
Содержание SS2 Series
Страница 21: ...Introduction of Shihlin Inverter Introduction of Inverter 17 3 5 5 System wire arrangement ...
Страница 174: ...Appendix 6 European Specification Compatibility Description Specification Description 170 CE Certification Statement ...
Страница 175: ...Appendix 6 European Specification Compatibility Description Specification Description 171 ...