Parameter Description
Parameter Description
87
Parameter
function
P.40/P.85
7
PO2 (Periodical detection): At the programmed operation mode, PO2 signal will
be output at the end of each cycle.
8
PO3 (Pause detection): At the programmed operation mode, PO3 signal will be
output when the inverter pauses.
9
BP (Inverter output): Switch between the inverter operation and commercial
power-supply operation function. During the inverter operation, BP will output
signals.
10
GP (Commercial power-supply output): Switch between the inverter operation and
commercial power-supply operation function. During the commercial
power-supply operation, GP will output signals.
11
OMD1(zero current detection): When the output frequency of inverters reach to
the target frequency and the percentage of the output current is lower than the set
value of P.62, OMD1 will output signal after a certain time set by P.63.
12
OL2 (Over torque alarm output): Please refer to over torque detection selection
P.260
17
RY (the inverter running preparation accomplishment): RY signal will be sendout
if inverter is in the state of being able to run.
18
Maintenance Alarm detection
• When P.120=0, the signal will be output directly if the set condition of P.40 (P.85) is met.
• When P.120=0.1~3600, the signal will be output after the set time if the set condition of P.40 (P.85)
is met.
For example: FU (Output frequency detection) function (For example: P.42/P.43=40Hz)