Parameter Description
Parameter Description
76
Modbus
Code
Item
Shihlin
Protocol
Code
Information Content and Functions
Modbus
Address
H03
Inverter State
H7A
H0000~H00FF
b8~b15
:
reserved
b7
:
Alarm occurrence
b6
:
Frequency detection
b5
:
Parameters to default values end.
b4
:
Overload
b3
:
Frequency achieved
b2
:
Reverse rotation
b1
:
Forward rotation
b0
:
Operation
H1001
H03
M
oni
tor
ing
Set
frequen
cy
EEPR
OM
H73
H0000~HFDE8
H1009
RAM
H6D
H1002
Output frequency
H6F
H0000~HFDE8
H1003
Output current
H70
H0000~HFFFF
H1004
Output voltage
H71
H0000~HFFFF
H1005
Alarm
item
H74
H0000~HFFFF:
H74/H1007
:
Error code 1 and 2
b15 b8 b7 b0
Error code 2
Error code 1
H75/H1008
:
Error code 3 and 4
b15 b8 b7 b0
Error code 4
Error code 3
Error code can reference the table in
alarm history parameters.
H1007
H75
H1008
H06/H1
0
Operation command
HFA
H0000~HFFFF
b8~b15: reserved
b7: scram
(
MRS
)
b6: 2
nd
Acceleration/Declaration
Selection(RT)
b5: High Speed (RH)
b4: Mid Speed (RM)
b3: :Low Speed (RL)
b2: REV Rotation(STR)
b1: FWD Rotation (STF)
b0: reserved
H1001
H06/H1
0
Inverter reset
HFD
H9696
:
The function of P.997
Communicate with the computer: the
inverter can not send data back to the
computer because it has been reset.
H1101