[3] THERMISTOR TEMPERATURE CHARACTERISTICS
1. Indoor unit thermistor temperature characteristics
2. Outdoor unit thermistor temperature characteristics
[4] HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
1. Cooling in 40 Hz fixed mode
To operate the outdoor unit independently, short-circuit the sections indicated by arrows in the diagram below with an adapter, and apply 230 VAC
between (1) and (N) on the terminal board of the outdoor unit. This allows the outdoor unit to be operated in cooling mode independently.
(Do not operate the outdoor unit in this condition for an extended period of time.)
K
100
80
60
40
20
0
-10
0
10
20
30
40
Heat exchanger thermistor TH2 (orange)
Resistance at 25 : 15 k
Resistance at 25 : 10 k
Room temperature thermistor TH1 (yellow)
-
+
Tester
Tester
4
3 2
1
-
+
Temperature( )
Resistance
(K )
CN2
TH1
TH2
CN2
Thermistor
Room temperature
Heat exchanger
Color
Yellow
Orange
Symbol
TH1
(CN2)
TH2
(CN2)
TH1 Room temperature thermistor
TH2 Heat exchanger thermistor
Before measuring resistance,
disconnect connectors as
shown above.
+
-
TH2 TH5
500K
400K
300K
200K
100K
0
-20
0
20
60
80
100 120
Tester
1
10
Connector
CN8
Resistance at 25
52.76 k
5.8K
40K
30K
20K
0
10K
-20
0
20
60
40
3.06K
4.17K
1.72K
2.28K
+
-
Tester
(In case of TH2 heat exchanger thermistor)
1
10
Connector
CN8
Thermistor
Compressor thermistor
Heat exchanger thermistor
Outdoor air temperature thermistor
No.
TH1
TH2
TH3
Connector
No. (1) - No. (2)
No. (3) - No. (4)
No. (5) - No. (6)
Color
Red
Orange
Green
TH1 Compressor thermistor
TH2 Heat exchanger thermistor
TH3 Outdoor air temperature thermistor
Resistance
(K )
Resistance
(K )
Temperature( )
Temperature( )
Resistance at 0
14.57 k
Resistance at 25
4.431 k
Before measuring resistance,
disconnect connectors from PWB.
(L2)
C9
C10
Connect with IC clip
Test mode cooling at 40 Hz
Connect with IC clip
Test mode cooling at 40 Hz
Short-circuit negative terminal of
capacitor (C33) and jumper wire
(JP16) using IC clip, etc.