[3] FUNCTION
1. Function
1.1. Restart control
Once the compressor stops operating, it will not restart for 180 sec-
onds to protect the compressor.
Therefore, if the operating compressor is shut down from the remote
control and then turned back on immediately after, the compressor will
restart after a preset delay time.
(The indoor unit will restart operation immediately after the ON switch
is operated on the remote control.)
1.2. Cold air prevention control
When the air conditioner starts up in heating mode, the indoor unit fan
will not operate until the temperature of the indoor unit heat exchanger
reaches about 23
°
C in order to prevent cold air from blowing into the
room.
Also, the indoor unit fan operates at low speed until the temperature of
the indoor unit heat exchanger reaches about 38
°
C so that people in
the room will not feel chilly air flow.
1.3. Indoor unit heat exchanger freeze prevention control
If the temperature of the indoor unit heat exchanger remains below
0
°
C for 4 consecutive minutes during cooling or dehumidifying opera-
tion, the compressor operation stops temporarily in order to prevent
freezing.
When the temperature of the indoor unit heat exchanger rises to 2
°
C
or higher after about 180 seconds, the compressor restarts and
resumes normal operation.
1.4. Outdoor unit 2-way valve freeze prevention control
If the temperature of the outdoor unit 2-way valve remains below 0
°
C
for 10 consecutive minutes during cooling or dehumidifying operation,
the compressor operation stops temporarily in order to prevent freez-
ing.
When the temperature of the 2-way valve rises to 10
°
C or higher after
about 180 seconds, the compressor restarts and resumes normal
operation.
1.5. Indoor unit overheat prevention control
During heating operation, if the temperature of the indoor unit heat
exchanger exceeds the indoor unit heat exchanger overheat preven-
tion temperature (about 45 to 54
°
C) which is determined by the operat-
ing frequency and operating status, the operating frequency is
decreased by about 4 to 15 Hz. Then, this operation is repeated every
60 seconds until the temperature of the indoor unit heat exchanger
drops below the overheat protection temperature.
Once the temperature of the indoor unit heat exchanger drops below
the overheat protection temperature, the operating frequency is
increased by about 4 to 10 Hz every 60 seconds until the normal oper-
ation condition resumes.
If the temperature of the indoor unit heat exchanger exceeds the over-
heat protection temperature for 60 seconds at minimum operating fre-
quency, the compressor stops operating and then restarts after about
180 seconds, and the abovementioned control is repeated.
1.6. Defrosting
1.6.1 Reverse defrosting
The defrost operation starts when the compressor operating time
exceeds 10 minutes during heating operation, as shown below, and
the outside air temperature and the outdoor unit heat exchanger tem-
perature meet certain conditions. When the defrost operation starts,
the indoor unit fan stops. The defrost operation stops when the out-
door unit heat exchanger temperature rises to about 10
°
C or higher or
the defrosting time exceeds 10 minutes.
1.7. Outdoor unit overheat prevention control
During cooling operation, if the temperature of the outdoor unit heat
exchanger exceeds the outdoor unit heat exchanger overheat preven-
tion temperature (about 55
°
C), the operating frequency is decreased
by about 4 to 15 Hz. Then, this operation is repeated every 60 sec-
onds until the temperature of the outdoor unit heat exchanger drops to
about 54
°
C or lower.
Once the temperature of the outdoor unit heat exchanger drops to
about 54
°
C or lower, the operating frequency is increased by about 4
to 10 Hz every 60 seconds until the normal operation condition
resumes.
If the temperature of the outdoor unit heat exchanger exceeds the out-
door unit heat exchanger overheat protection temperature for (120 sec
: outdoor temperature
≥
40
°
C, 60 sec : outdoor temperature < 40
°
C)
at minimum operating frequency, the compressor stops operating and
then restarts after about 180 seconds, and the abovementioned con-
trol is repeated.
Compressor operation
ON operation on
remote control
OFF operation on
remote control
Compressor ON
Compressor ON
Compressor can
turn ON
Compressor remains OFF
for 180 seconds
Indoor unit heat exchanger temperature
38
23
35
21
Set fan speed
Indoor unit fan at low speed
Indoor unit fan in non-operation
20 min or more
20 min or more
20 min or more
Defrosting
Max. 10 min
Defrosting
Max. 10 min
Start of
heating
operation