Page 32 of 36
www.sgm-lektra.com
FLOWMETER -
configuration
8.7
SERVICE menu
8.8 - SERVICE
Press SCROLL to select the menu and press ENTER to access.
Press LEFT ARROW to exit.
SETUP
DISPLAY
FLOW APPL.
SERVICE
INFO
►
8.8.1 - OUTPUT SAFE MODE
Position the cursor on OUTPUT SAFE MODE, press ENTER to confirm
It’s possible to choose a analog output value during diagnostic errors.
“21.5 mA” forces the current output to 21,5mA
“3.85 mA” forces the current output to 3,85mA
”HOLD LAST VALUE” maintains the output at the last valid value.
With the SCROLL button you can select the operation mode.
Press ENTER to confirm. LEFT ARROW to exit without changes
Default value: HOLD LAST VALUE
OUTPUT SAVE MODE
SET UID
LANGUAGE
OUTPUT SIMULATION
F. WINDOW
RESTORE SETTING
►
21.5 mA
3.85 mA
HOLD LAST VALUE
►
8.8.2 - SET UID
Position the cursor on SET UID, press ENTER to access.
Can assign the address UID in this parameter, for a MUDBUS RTU network.
Use UP ARROW and SCROLL to modify the value.
Press ENTER to confirm.
LEFT ARROW to exit without changes
Default value 001
OUTPUT SAVE MODE
SET UID
LANGUAGE
OUTPUT SIMULATION
F. WINDOW
RESTORE SETTING
►
001
SET UID
SERVICE
S ET UID
OUTPUT SAFE MODE
LANGUAGE
OUTPUT SIMUL.
S ET UID
001
21.5 mA
3.85 mA
HOLD LAST VALUE
ENGLISH
ITALIANO
FRANCAIS
OUTPUT
00.0 mA
F_WINDOW
F_WINDOW
05
RESTORE SETTINGS
OK TO CONFIRM