Page 16 of 36
www.sgm-lektra.com
FLOWMETER -
configuration
8.2.3.2 - MIN/MAX
Position the cursor on MIN/MAX, press ENTER to confirm
It’s possible to select if the relay works as minimum flow rate
or maximum flow rate threshold.
Press SCROLL button to select the operation mode.
Press ENTER to confirm. LEFT ARROW to exit without changes
Default value: MAX
MAX
MIN
►
VALUE
MIN / MAX
DELAY
SAFETY
ENABLE / DISABLE
►
8.2.3.3 - DELAY
Position the cursor on DELAY, press ENTER to confirm
It’s possible to select the activation delay for the RL2, from 0 to 99 sec.
Use UP ARROW and SCROLL to modify the value.
Press ENTER to confirm. LEFT ARROW to exit without changes
Default value: 00s
00 s
DELAY
VALUE
MIN / MAX
DELAY
SAFETY
ENABLE / DISABLE
►
8.2.3.4 - ENABLE/DISABLE
Position the cursor on ENABLE/DISABLE, press ENTER to confirm
Select ENABLE to activate RL2 threshold.
Select DISABLE to not RL2 relay threshold.
Press SCROLL button to select the operation mode.
Press ENTER to confirm. LEFT ARROW to exit without changes
Default value: ENABLE
DISABLE
ENABLE
►
VALUE
MIN / MAX
DELAY
SAFETY
ENABLE / DISABLE
►
8.2.3.3 - SAFETY
Position the cursor on SAFETY, press ENTER to confirm
A “safety alarm” provides a “closed” contact with relay energized
in normal condition (no alarm), the contact switches to “open”:
- Alarm condition (eg overcoming MAX);
- In power failure case.
Press SCROLL button to select the alarm mode.,
Press ENTER to confirm. LEFT ARROW to exit without changes
Default value: YES
NO
YES
►
VALUE
MIN / MAX
DELAY
SAFETY
ENABLE / DISABLE
►