6
Electrical installation
Cable routing
Operating Instructions – MOVIPRO
®
PHC2.A-A..M1-E45C-C5
60
6.6
Cable routing
Observe the following when routing the cables:
•
Use suitable cables to connect power supply and communication. For more infor-
mation on connection descriptions, refer to chapter "Electrical connec-
tions" (→
•
Route power cables and signal cables in separate cable ducts.
•
Maintain the greatest possible distance between power cables and signal cables.
•
Avoid using long cables running parallel to one another.
For further information on EMC compliant installation, refer to the following documen-
tation: "Drive Engineering – Practical Implementation, Electromagnetic Compatibility
(EMC) in Drive Engineering".
6.7
Shielding
•
Use shielded power and electronics cables.
•
Connect the shield and make sure it is grounded over a wide area at both ends.
When using cables with multiple shielding, also make sure that the inner shields
are grounded over a wide area at both ends.
•
Use EMC-capable plug connectors.
•
For external bus connections, refer to the bus-specific installation instructions.
6.8
Protective measures against electrical hazards
6.8.1
Overview
Preventive measures according to IEC 60364‑4‑41
Stationary use
Mobile application
Direct power supply
Ground connection
24171709707
26596598/EN – 10/2020