7
Service
Error list
Compact Operating Instructions – MOVIMOT
®
MM..D with AS-Interface
59
7.2
Error list
The following table helps you with troubleshooting:
Code
Error
Possible cause
Measure
–
Communication
timeout
(motor stops, without
error code)
No connection
⍊
, RS+, RS-
between MOVIMOT
®
and
RS485 master
Check and establish connection, especially
earth.
EMC influence
Check shielding of data lines and improve, if
necessary.
Incorrect type (cyclical) for
acyclical data traffic, proto-
col period between the in-
dividual telegrams is longer
than the timeout set.
Check number of MOVIMOT
®
drives connec-
ted to the master. If a timeout period of 1 s, for
example, a maximum of 8 MOVIMOT
®
drives
may be connected as slaves with cyclical com-
munication.
Reduce telegram cycle, increase timeout peri-
od or select telegram type "acyclic".
–
Supply voltage not
present
(motor stops, without
error code)
DC link voltage too high,
supply system off has been
recognized
Check power cables and line voltage for inter-
ruption.
–
24 V supply not
available
(motor stops, without
error code)
24 V supply voltage not
available
Check 24 V supply voltage for interruption
Check value of 24 V supply voltage.
Permitted voltage: DC 24 V ± 25%,
EN 61131-2, residual ripple max. 13%
Motor restarts automatically as soon as the
voltage reaches normal values.
AUX power supply voltage
not available.
(only for MOVIMOT
®
with
AS-interface)
AUX power supply voltage not available
Check value of AUX power supply voltage.
Permitted voltage: DC 24 V ± 25%,
EN 61131-2, residual ripple max. 13%)
Motor restarts automatically as soon as the
voltage reaches normal values.
01
Overcurrent in out-
put stage
Short circuit on inverter
output
Check the connection between the inverter
output and the motor as well as the motor
winding for short circuits.
Reset error.
1)
04
Brake chopper
Overcurrent in brake out-
put, resistor damaged, re-
sistance too low.
Check the connection of the resistor/replace it.
Short circuit, brake coil
Replace brake.
06
Phase failure
(error can only be de-
tected when drive is
under load)
Phase failure
Check the supply system cables for phase fail-
ure.
Reset error
1)
.
21328994/EN – 11/2014