5.2.5
Information on PE connection
WARNING
Electric shock due to incorrect connection of PE.
Severe or fatal injuries.
• The permitted tightening torque for the screw is 2.0 – 2.4 Nm (18 – 21 lb.in).
• Observe the following notes regarding PE connection.
Prohibited assembly pro-
cedure
Recommendation:
Assembly with forked cable lug
Permitted for all cross sections
Assembly with solid connecting
wire
Permitted for cross sections of up
to max. 2.5 mm
2
9007199577783435
[1]
M5
9007199577775243
2.5 mm²
M5
9007199577779339
[1]
Forked cable lug suitable for M5 PE screws
Leakage currents ≥ 3.5 mA can occur during normal operation. To meet the require-
ments of EN 61800-5-1, observe the following notes:
• The protective earth (PE) connection must meet the requirements for plants with
high earth-leakage currents.
• This usually means
– installing a PE connection cable with a minimum cross section of 10 mm
2
– or installing a second PE connection cable in parallel with the original PE con-
nection.