7
Service
Status and error display
Compact Operating Instructions – MOVIMOT
®
MM..D with AS-Interface
58
LED
Color
Status
Meaning
Operating sta-
tus Error code
Possible cause
Red
flashes slowly
Error 08
Speed monitoring error (only when S2/4 = "ON")
or additional function 13 is active.
Error 09
Startup error
Additional functions 4, 5, 12 (DIP switches S2/5 – S2/8) are
not permitted.
Error 15
Error 24 V supply
Errors 17 – 24,
37
CPU errors
Errors 25, 94
EEPROM error
Errors 38, 45
Unit/motor data error
Error 44
Current limit exceeded for longer than 500 ms (only for addi-
tional function 2)
Fault 90
Motor – inverter assignment is incorrect.
Error 97
Error during transmission of the parameter set
Error 99
Firmware does not support MLK31A option
(only for MOVIMOT
®
with AS-interface).
Red
3 x flashing, break
Error 01
Overcurrent in output stage
Error 11
Overtemperature in output stage
Red
4 x flashing, break
Error 84
Overload in motor
Red
5 x flashing, break
Error 4
Error brake chopper
Error 89
Overtemperature in brake
Motor – frequency inverter assignment is incorrect.
The brake and braking resistor are connected to terminals
X1:13 – X1:15 at the same time. This is not permitted.
Red
6 x flashing, break
Error 06
Line phase failure
Error 81
Start condition
1)
Error 82
Output phases interrupted.
1)
Red
constantly lit
Not ready
Check 24 V supply.
A smoothed DC voltage with maximum residual ripple of 13%
must be present.
1) for lifting applications only
Status LED flash codes
Flashing evenly:
LED 600 ms on, 600 ms off
Flashing evenly, fast:
LED 100 ms on, 300 ms off
Flashing with alternating colors:
LED 600 ms green, 600 ms yellow
Flashing with alternating colors, break:
LED 100 ms green, 100 ms red, 100 ms green, 300 ms break
N x flashing, break:
LED N x (600 ms red, 300 ms off), then LED off for 1 s
21328994/EN – 11/2014