Electrical installation
Installation instructions
Compact Operating Instructions – MOVIMOT
®
MM..D with AS-Interface
22
5.2.3
Residual current device
WARNING
Electric shock due to incorrect RCD type.
Severe or fatal injuries.
• The unit can cause direct current in the protective earth. In cases where an resid-
ual current device (RCD) is used for protection against direct or indirect contact,
only an RCD of type B on the power supply side of the frequency inverter is per-
mitted.
• Do not use a conventional RCD as a protective device. Universal current-sensitive
RCDs are permitted as a protective device. During normal operation of the unit,
earth-leakage currents of > 3.5 mA may occur.
• SEW
‑
EURODRIVE recommends that you do not use residual current devices.
However, if a residual current device (RCD) is stipulated for direct or indirect pro-
tection against contact, observe the above note.
5.2.4
Line contactor
NOTICE
Damage to the MOVIMOT
®
inverter due when using the line contractor K11 for jog
mode.
Damage to the MOVIMOT
®
inverter.
• Do not use the K11 line contactor (see wiring diagram) for jog mode, but only for
switching the inverter on and off. For jog mode, use the commands "CW / Stop"
or "CCW / Stop".
• Observe a minimum switch-off time of 2 s for the input contactor K11.
• Only use a contactor of utilization category AC3 (EN 60947-4-1) as a line contac-
tor.