5
Electrical Installation
Standard ABOX "MTA...-S02.-...-00"
Operating Instructions – MOVIFIT
®
-FC
45
5.4.3
Additional installation instructions for "MTA...-S02.-...-00"
Permitted connection cross section and current-carrying capacity of the terminals
Conductor end
sleeves
Use conductor end sleeves without insulating shrouds for terminals X1, X20, X8, and X9
(DIN 46228 part 1, material E-CU).
Terminal data
X1 / X20
X8 / X9
X25 / X30 / X31 / X35 / X45 /
X81 / X91
X29
Connection cross
section (mm
2
)
0.2 mm
2
– 6 mm
2
0.08 mm
2
– 4
1)
mm
2
1) The maximum permitted cross section is reduced by one unit when conductor end sleeves are used (e.g. 2.5 mm
2
Æ
1.5 mm
2
).
0.08 mm
2
– 2.5
1)
mm
2
0.2 mm
2
– 1.5
1)
mm
2
Connection cross
section (AWG)
AWG 24
–
AWG 10
AWG 28 – AWG 12
1)
AWG 28 – AWG 14
1)
AWG 24 – AWG 16
1)
Current-carrying
capacity (max.
continuous current)
X1: 32 A
2)
X20: 16 A
2) According to standard EN 61800-5-1, the temperature of the connection terminals may be 15°C above the permitted rated temperature
of the performance isolation. Therefore, you may use only connection cables that are heat resistant up to 90°C. As an alternative, you
can to limit the looping current.
20 A
10 A
10 A
Conductor stripping
length
13-15 mm
8-9 mm
5-6 mm
5-6 mm