6
Startup
Startup MOVIFIT®
102
Operating Instructions – MOVIFIT
®
-FC
6.3.2
Startup with PROFINET IO, EtherNet/IP, or Modbus/TCP
1. Check the MOVIFIT
®
connection.
2. To start up the MOVIFIT
®
inverter, see the section "Startup MOVIFIT
®
Frequency
Inverter" (see page 104).
3. Set DIP switch S11/2 "DEFIP" to "ON".
This sets the address parameters to the following default values:
4. Mount the MOVIFIT
®
-EBOX on the ABOX and close it.
5. Switch on the 24V_C and 24V_S supply voltage(s). The associated control LEDs
should now light up green.
TIP
In conjunction with PROFINET IO, EtherNet/IP, or Modbus/TCP, you do not have to
make any settings on the MOVIFIT
®
for fieldbus startup. The entire fieldbus startup is
carried out via Software Tools and is described in the applicable manuals:
• Manual for MOVIFIT
®
function level "Classic..."
1)
• "MOVIFIT
®
Function Level Technology..."
1)
manual
1) The "MOVIFIT
®
Function Level Classic" and "MOVIFIT
®
Function Level Technology" manuals are available in several fieldbus-specific
versions.
DIP switch S11/2 = ON
MOVIFIT
®
function level
"Technology"
MOVIFIT
®
function level "Classic"
1167697803
1167754379
IP address:
192.168.10.4
Subnet mask:
255.255.255.0
Gateway:
0.0.0.0
1
ON
4
3
2
S11
DHCP
DEF IP
res. (OFF)
res. (OFF)
1
ON
2
S11
res. (OFF)
DEF IP
0
0
I