Description of DIP
switches S10/2 to
S10/6
In Easy mode, the unit parameters are set using the DIP switches S10/2 to S10/6.
The following sections describe the setting options:
DIP switch S10/2
Control modes
• DIP switch S10/2 = OFF: VFC operation for 4-pole motors
• DIP switch S10/2 = ON: V/f operation for other motors
DIP switch S10/3
Motor/brake type
• When you are using IEC or NEMA motors (DT/DV), DIP switch S10/3 must always
be set to OFF.
• For DX/DZ motors with rated voltages of 220/380 V, 60 Hz (only available in Brazil),
and for aseptic motors (DAS), DIP switch S10/3 must be set to ON.
• When you are using DR motors with MOVIFIT
®
standard brakes, DIP switch S10/3
must always be set to OFF.
• When you are using DR motors with option brakes, DIP switch S10/3 must always
be set to ON.
DIP switch S10/4
Motor connection type
• DIP switch S10/4 = OFF: You must select this setting if the motor is operated in star
connection (refer to the tables on the following pages).
• DIP switch S10/4 = ON: You must select this setting if the motor is operated in delta
connection (refer to the tables on the following pages).
837604491
S10
1
2
3
4
5
6
Meaning
Startup
mode
Operating
mode
Motor/brake
type
Motor
connection
type
Motor
power
Hoist
ON
Expert
mode
V/f
Motor type
2/Option brake
Delta
One power
rating lower
VFC/Hoist
OFF
Easy mode
VFC
operation
(only for
4-pole SEW
motors)
Motor 1/
Standard brake
Star
Adjusted
S10/2
active
1
6
5
4
3
2
S10
ON
CAUTION
Set the DIP switches using suitable tools, e.g. a slotted screwdriver with a blade width
smaller than 3 mm.
The force used for setting the DIP switches must not exceed 5 N.
0
0