Operating display of the DHP11B control card
Assembly / Installation Instructions
CAN 2 status LED
The CAN 2 status LED indicates the status of the CAN 2 system bus.
CAN 1 status LED
The CAN 1 status LED indicates the status of the CAN 1 system bus.
CAN 2
status
Diagnostics
Remedy
Orange
•
The CAN 2 system bus is being initialized.
-
Green
•
The CAN 2 system bus is initialized.
-
Flashing
green
(0.5 Hz)
•
The CAN 2 system bus is currently in
SCOM suspend mode.
-
Flashing
green
(1 Hz)
•
The CAN 2 system bus is currently in
SCOM On mode.
-
Red
•
The CAN 2 system bus is off (BUS-OFF).
1.
Check and correct the cabling of the CAN
2 system bus.
2.
Check and correct the baud rate set for
the CAN 2 system bus.
3.
Check and correct the terminating resis-
tors of the CAN 2 system bus.
Flashing
red
(1 Hz)
•
Warning on the CAN 2 system bus.
1.
Check and correct the cabling of the CAN
2 system bus.
2.
Check and correct the baud rate set for
the CAN 2 system bus.
CAN 1
status
Diagnostics
Remedy
Orange
•
The CAN 1 system bus is being initialized.
-
Green
•
The CAN 1 system bus is initialized.
-
Flashing
green
(0.5 Hz)
•
The CAN 1 system bus is currently in
SCOM suspend mode.
-
Flashing
green
(1 Hz)
•
The CAN 1 system bus is currently in
SCOM On mode.
-
Red
•
The CAN 1 system bus is off (BUS-OFF).
1.
Check and correct the cabling of the CAN
1 system bus.
2.
Check and correct the baud rate set for
the CAN 1 system bus.
3.
Check and correct the terminating resis-
tors of the CAN 1 system bus.
Flashing
red
(1 Hz)
•
Warning on the CAN 1 system bus.
1.
Check and correct the cabling of the CAN
1 system bus.
2.
Check and correct the baud rate set for
the CAN 1 system bus.